Suction Riser —
A suction riser condition exists when the outdoor unit is
located above the indoor (evaporator) unit and suction
vapor must flow vertically up to return to the compressor.
Oil return is a concern when the suction tube size is too
large to produce the minimum refrigerant velocity to
ensure oil return at minimum load conditions.
Check Table 7 for maximum suction tube size for 38AU
units at minimum load conditions. Consider suction speed
riser (reduced tube size for vertical segment only) or
double suction riser arrangement if the proposed suction
tube size does not provide necessary minimum flowrates
for this riser.
Table 7 –
38AU Maximum Suction Pipe Size
Model:
Unit Size
38AUZ
07
08
38AUD
12
14
Vertical Separation (outdoor unit above indoor unit) –
Vertical elevation difference of 60 m (200 ft) is permitted
when the outdoor unit (38AUZ or 38AUD) is located
above the indoor unit.
Insulate Suction Lines —
Apply closed-cell tubular insulation to all suction lines
between evaporator coil connection and 38AU unit's
suction service valve.
Hot Gas Bypass —
Hot gas bypass, if used, should be introduced before the
evaporator. (A bypass route that also bypasses the
evaporator circuit may lead to oil trapping in the
evaporator circuit during low load conditions and then to
oil slugging as evaporator load increases.) Model 38AU
units do not include a hot gas stub connection; a tee must
be field-supplied and installed in the compressor discharge
1
line. Run a
/
-in OD line between outdoor unit and
2
evaporator coil inlet. Install an Auxiliary Side Connector
at the evaporator between TXV and distributor (follow
instructions for the side connector part). Insulate the hot
gas line.
38AUD: Generally only one hot gas bypass system will be
applied on a two-circuit unit. Connect the hot gas bypass
system to Circuit 1 (first-on/last-off, connected to the
evaporator coil's bottom circuit).
38AUD Piping Connections —
The 38AUD's two circuits are designated Circuit 1 and
Circuit 2. Circuit 1 is controlled by the thermostat's Y1
(or TC1) contact and will be the first circuit on and last
circuit off. Circuit 2 is controlled by the thermostat's Y2
Maximum Tube Size
3
1
/
8
5
1
/
8
3
1
/
8
3
1
/
8
(or TC2) contact and this circuit is always the "lag"
circuit.
See Fig. 5 for location of Circuit 1 and Circuit 2 service
valves and field piping connections. Circuit 1 is on the
right-hand side of the service valve compartment; Circuit
2 is on the left.
When a single piece evaporator coil with two separate
circuits is connected to a 38AUD, the lower coil circuit
should be connected to the 38AUD's Circuit 1 so that the
evaporator's lower coil segment is first-on/last-off (to
avoid re-evaporation of condensate on dry lower coil
segments).
CKT
2
CKT
1
Fig. 5 - - 38AUD Service Valve Locations
Plan the Circuit 1 and Circuit 2 tubing segments carefully,
mark each segment and check constantly as piping
systems are assembled to avoid piping errors.
38AUD
unit
cannot
single-circuit/tandem system.
Connecting 40RU to 38AUD: The 40RU fan coil in sizes
12, 14 and 16 is a face-split coil design that also has its
circuits designated as 1 and 2. See Fig. 6. Note that the
lower coil segment changes as the arrangement of the
40RU changes. In a vertical arrangement, the 40RU's
lower coil segment is segment 2; this segment should be
connected to the 38AUD's Circuit 1. In a horizontal
arrangement, the 40RU's lower segment is now segment
1; this segment should be connected to the 38AUD's
Circuit 1.
Note that refrigerant suction piping should be insulated.
40RU
Cooling
Arrangement
Stage
Y1
Vertical
Y2
Y1
Horizontal
Y2
14
Circuit 1
Connections
Circuit 2
Connections
C10912
be
field-piped
as
40RU Coil
Connect to
Segment
38AUD
2
Circuit 1
1
Circuit 2
1
Circuit 1
2
Circuit 2
a