1. Electrical Wiring
CAUTION
(1)
When linking the outdoor units in a network, disconnect the terminal extended from the short plug from
all outdoor units except any one of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2)
Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit
1
Indoor unit
2
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address
setting.
3
4
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
5
6
7
8
9
Outdoor unit
Indoor unit
Outdoor unit
NO
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch point
: Branch point
Indoor unit
Indoor unit
Indoor unit
2-4
Design of VRF SYSTEM
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Fig. 2-2
Fig. 2-3
Fig. 2-4