Indoor Heat Exchanger - Daikin FTXZ09NV1S Service Manual

Table of Contents

Advertisement

Indoor Heat Exchanger

8. Indoor Heat Exchanger
Warning
Caution
Step
1. Detach the indoor unit.
1
Remove the 2 screws
which fix the indoor unit
to the installation plate.
2
Unfasten the 2 hooks
and detach the indoor
unit from the installation
plate.
2. Remove the air filter
guide.
Unfasten the 3 hooks
1
and remove the air filter
guide.
26
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
In pump-down work, be sure to stop the compressor before disconnecting the
refrigerant pipe. If the refrigerant pipe is disconnected with the compressor operating
and the stop valve open, air may be sucked in and may generate an over-pressure in
refrigeration cycle, thus resulting in pipe rupture or accidental injury.
When removing or reinstalling the indoor heat exchanger, be sure to wear gloves or
wrap the indoor heat exchanger with cloths. (You may be injured by the fins.)
Be sure to conduct pump down operation before disassembling the refrigerant pipe.
If the refrigerant leaks, repair the spot of leaking, then collect all refrigerant from the
unit. After conducting vacuum drying, recharge proper amount of refrigerant.
From the viewpoint of global environmental protection, make sure to use a vacuum
pump for air purging.
Procedure
Hook
Hook
Air filter guide
Hook
(R19905)
Hook
(R19906)
Hook
(R20729)
Si041411E
Points
There are 2 hooks on the
back of the air filter guide.
When reassembling, make
sure to fit the hooks.
Removal Procedure