G3G180-AD43-71

3.2 Nominal data

Motor
M3G084-FA
Phase
1~
Nominal voltage / VAC
230
Nominal voltage
200 .. 277
range / VAC
Frequency / Hz
50/60
Method of obtaining
ml
data
-1
Speed (rpm) / min
2450
Power consumption / W
510
Current draw / A
3.15
Min. back pressure / Pa
300
Min. ambient
-25
temperature / °C
Max. ambient
50
temperature / °C
ml = Max. load · me = Max. efficiency · fa = Free air
cs = Customer specification · ce = Customer equipment
Subject to change
3.3 Data according to Commission Regulation (EU) 327/
2011
01 Overall efficiency η
/ %
es
02 Measurement category
03 Efficiency category
04 Efficiency grade N
05 Variable speed drive
06 Year of manufacture
07 Manufacturer
08 Type
09 Power consumption P
/ kW 0.31
ed
09 Air flow q
/ m³/h
v
09 Pressure increase total p
/
sf
Pa
10 Speed (rpm) n / min
-1
11 Specific ratio
*
12 Recycling/disposal
13 Maintenance
14 Additional components
*
Specific ratio = 1 + p
/ 100 000 Pa
fs
Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller
combination in a standardized measurement setup.
Item no. 50780-5-9970 · ENU · Change 213992 · Approved 2020-07-14 · Page 5 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Actual
Req. 2015
46.4
34.5
A
Static
55.9
44
Yes
The year of manufacture is specified on the
product's rating label.
ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen
G3G180-AD43-71
760
628
2605
1.01
Information on recycling and disposal is
provided in the operating instructions.
Information on installation, operation and
maintenance is provided in the operating
instructions.
Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

3.4 Technical description

Weight
6.9 kg
Size
180 mm
Motor size
84
Rotor surface
Painted black
Electronics housing
Die-cast aluminum
material
Impeller material
Sheet steel, galvanized
Housing material
Sheet steel, galvanized
Direction of rotation
Clockwise, viewed toward rotor
Degree of protection
IP54
Insulation class
"B"
Moisture (F) /
H1
Environmental (H)
protection class
Installation position
Shaft horizontal or rotor on top; rotor on
bottom on request
Condensation
None
drainage holes
Mode
S1
Motor bearing
Ball bearing
Technical features
- Output 10 VDC, max. 1.1 mA
- Alarm relay
- Motor current limitation
- PFC, passive
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for
electronics/motor
- Line undervoltage detection
Touch current
<= 3.5 mA
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)
Motor protection
Thermal overload protector (TOP)
internally connected
with cable
Variable
Protection class
I (with customer connection of protective
earth)
Conformity with
EN 61800-5-1; CE
standards
Approval
EAC; CCC; CSA C22.2 No. 77 +
CAN/CSA-E60730-1; UL 1004-3 +
60730-1
With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.
; Use the device in accordance with its degree of protection.