K3G310-AI39-71

3.2 Nominal data

Motor
M3G084-DF
Phase
1~
Nominal voltage / VAC
230
Nominal voltage
200 .. 277
range / VAC
Frequency / Hz
50/60
Type of data definition
ml
-1
Speed / min
2250
Power input / W
500
Current draw / A
3.15
Min. ambient
-25
temperature / °C
Max. ambient
30
temperature / °C
ml = max. load · me = max. efficiency · fa = running at free air
cs = customer specs · cu = customer unit
Subject to alterations

3.3 Data according to ErP directive

Installation category
Efficiency category
Variable speed drive
Specific ratio
*
*
Specific ratio = 1 + p
/ 100 000 Pa
fs
Overall efficiency η
es
Efficiency grade N
Power input P
/ kW
ed
Air flow q
/ m³/h
v
Pressure increase total p
/ Pa
sf
Speed n / min
-1
Data established at point of optimum efficiency

3.4 Technical features

Mass
7.53 kg
Size
310 mm
Surface of rotor
Coated in black
Material of electronics
Die-cast aluminium
housing
Material of impeller
Aluminium sheet
Material of mounting
Aluminium sheet
plate
Material of distancing
Aluminium
profiles
Number of blades
6
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 54
Insulation class
"B"
Humidity class
F3-1
Mounting position
Shaft horizontal or rotor on top; rotor on
bottom on request
Condensate discharge
None
holes
Operation mode
S1
Item no. 51002-5-9970 · Revision 72357 · Release 2010-12-07 · Page 5 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
A
Static
Yes
1.00
Actual
Request
Request
2013
2015
57.2
44.2
48.2
71
58
62
0.48
2005
450
2175
Motor bearing
Ball bearing
Technical features
- Output 10 VDC, max. 1.1 mA
- Alarm relay
- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor
- Line undervoltage detection
Touch current acc.
<= 3.5 mA
IEC 60990 (measuring
network Fig. 4, TN
system)
Motor protection
Thermal overload protector (TOP) wired
internally
Cable exit
Variable
Protection class
I (if protective earth is connected by
customer)
Product conforming
EN 61800-5-1; CE
to standard
Approval
UL 2111; CSA C22.2 Nr.77
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
8.8
mounting screws
You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

; Use the device in accordance with its protection type.
Max. permissible
+80 °C
ambient motor temp.
(transp./ storage)
Min. permissible
-40 °C
ambient motor temp.
(transp./storage)

3.7 Electromagnetic compatibility

EMC interference
Acc. to EN 61000-6-2 (industrial
immunity
environment)
EMC harmonics
Acc. to EN 61000-3-2/3
EMC interference
Acc. to EN 61000-6-3 (household
emission
environment)

Advertisement