1-2 Major Component Specifications

Controller PCB
Model
Controls
Control Circuit Fuse (F1)
Jumper Setting JP1 ... JP5
Remote Control Unit
Thermistor Coil Sensor
Resistance at 25°C
Thermistor Room Sensor (TH Room)
Resistance at 25°C
Fan Motor Indoor Unit (FMI)
Model
Number / Diameter / Length
No. Of Pole - RPM High/Med./Low (230V)
Nominal Input
Coil Resistance at 25°C
Safety Device
Setting
Run Capacitor (C)
Fan Motor Outdoor Unit (FMO)
Model
Diameter
No. Of Pole / RPM (230V)
Nominal Input
Coil Resistance at 25°C
Safety Device
Setting
Run Capacitor (C)
Compressor
Model
Nominal Cooling Capacity
Compressor Oil: RB68A or Freol Alpha68M
Compressor Oil: DAPHNE FV68S or equivalent
Coil Resistance
Run Capacitor (C)
Overload Relay (OLR)
Operating Temperature
Short Time Trip
Operating temp. Open
Close
Operating temp. Open
Close
at 20°C
*at 25°C
Open
Close
6-16 Sec. At 25°C
5
SMDF117C5TAA
SAC ON-OFF IDU
250VAC - 3,15A - T
2,54mm - 5 pcs
NTC (with Brass Pipe)
kΩ
kΩ
K35407-MO2018
Cross-Flow / Ø 125 / 295
mm
4 - 1120/990/830
W
GRY-WHT: 394 ± 5%
WHT-VLT: 107 ± 5%
VLT-ORG: 107 ± 5%
ORG-PNK: 107 ± 5%
GRY-BRN: 122 ± 5%
Internal Bimetallic Type
°C
0,6
µF
VAC
K35410-MO1515
Ø 280
mm
4 / 1200
61
W
BLU-BRN: 249÷287± 5% BLU-BRN: 218÷251± 5%
BLU-BLK: 270÷311± 5%
Internal Bimetallic Type
°C
2,0
µF
VAC
Rotary (Hermetic)
5PS112EBA
3166
W
350
cc
---
cc
C-R : 3166
C-S : 4573
25
µF
450
VAC
140 ± 5%
°C
75 ± 11%
°C
19,5
A
DATA SUBJECT TO CHANGE WITHOUT NOTICE
SMDF147C5TAA
SMDF141C5TAA
Microprocessor
SAC WREM
10 ± 3%
10 ± 5%
4 - 1235/1125/980
14
150 ± 10
Autoreset
1,0
440
K35610-MO1525
Ø 340
6 / 860
70
BLU-BLK: 230÷265± 5%
150 ± 10
Autoreset
2,5
450
80235455
3680
---
520
*C-R : 2402
*C-S : 3582
30
450
External
150 ± 5%
69 ± 11%
23,5