11-7. Inspection of the Main Parts
[1] Sensor characteristic table
100
90
80
70
60
50
40
30
20
10
0
0
10
Outdoor Unit
No.
Part name
1
Compressor
RAS-2M14U2AVG-E,-TR
(Model : KTN130D30UFZ)
RAS-2M18U2AVG-E,-TR
RAS-3M18U2AVG-E,-TR
(Model : DX136A1T-40N)
2
Outdoor fan motor
(Model : WDF-340-A43-1)
3
Compressor thermo. Bimetal
type (Model : CS-12AL) For
RAS-2M18U2AVG-E,-TR
RAS-3M18U2AVG-E,-TR
4
High pressure switch
(Model : ACB-4UB83W)
5
Outdoor temperature sensor (TO),
pipe temperature sensor
(TGa, TGb, TGc),
discharge temperature sensor (TD),
suction temperature sensor (TS),
evaporator temperature sensor (TE),
TD
TO, TE, TS, TGa to TGc
20
30
40
50
Temperature (˚C)
Measure the resistance value of each winding by using the tester.
Red
White
Measure the resistance value of winding by using the tester.
White
Check conduction by using the tester.
Check conduction by using the tester.
Disconnect the connector, and measure resistance value with the
tester.(Normal temperature)
Sensor
TO, TE, TS (kΩ)
TGa to TGc (kΩ)
TD
: Discharge temp. sensor
TO
: Outdoor temp. sensor
TE
: Outdoor heat exchanger temp.
sensor : Suction temp. sensor
TS
TGa to TGc : Gas side temp. sensor
Checking procedure
Position
Red - White
White - Black
Black - Red
Black
Red
Position
Red - White
White - Black
Black - Red
Black
Temperature
10°C
TD (kΩ)
105
20.6
20.0
- 101 -
FILE NO. SVM-18020
Resisitance value
KTN130D30UFZ
DX136A1T-40N
0.68Ω
3.19Ω
Under 20°C
Resistance value
33 ± 1.7Ω
For details, refer to Section 11-8.
20°C
25°C
40°C
64
51
27
12.6
10.0
5.1
12.5
10.0
5.3
50°C
18
3.4
3.6