CAUTION
New refrigerant air conditioner installation
• This air conditioner adopts the new HFC refrigerant
(R410A) which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb
water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with
the new refrigerant, refrigerating oil has also been changed.
Therefore, do not let water, dust, former refrigerant, or
refrigerating oil enter the refrigerating cycle during installation
work.
• To prevent charging an incorrect refrigerant and refrigerating
oil, the sizes of connecting sections of charging port of the
main unit and installation tools are changed from those for the
conventional refrigerant.
• Accordingly the exclusive tools are required for the new
refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for
R410A, and please care so that water or dust does not enter.
To disconnect the appliance from main power supply.
• This appliance must be connected to the main power supply by
means of a switch with a contact separation of at least 3 mm.
The installation fuse (all types can be used) must be used for
the power supply line of this conditioner.
(*1) Refer to the "Defi nition of Qualifi ed Installer or Qualifi ed
Service Person."
13-EN
– 7 –
2

Accessory parts

Accessory parts
Part name
Q'ty
Installation Manual
1
CD-ROM
1
Heat insulating pipe
2
Installation pattern
1
Installation gauge
– –
Washer
4
Eccentric washer
4
Hose band
1
Flexible hose
1
Heat insulator
1
Separate sold parts
The Ceiling panel and remote controller are sold separately. For the installation of these products, follow the
Installation Manuals supplied with them.
The wireless type remote controller is designed to be installed by attaching a wireless remote controller kit (sold
separately) to the standard panel. (The wireless remote controller kit consists of a wireless remote controller and
adjust corner caps with a receiver section.)
Shape
Usage
(Hand over to customers)
This manual
(For other languages that do not appear in this Installation
Manual, please refer to the enclosed CD-R.)
Installation Manual
For heat insulation of pipe connecting section
For confirmation of ceiling opening and indoor unit position
For positioning of ceiling position
For hanging-down unit
For hanging-down unit
For connecting drain pipe
For adjusting center of drain pipe
For heat insulation of drain connecting section