The burner control unit FIRO is suitable for the control
of industrial burners up to 350 kW, pursuant to EN
746-2, for intermittent or continuous operation.
Flame control by means of ionization rod (even shared
with ignition).
Advanced self-diagnostic system provides the display
of either the cycle status, the causes that produced
lockouts or the immediate diagnostic of the failures
that affect the equipment or the burner.
Firo provides lockout output and remote reset input.
Times and operating cycle are configurable: the same
device can be used to control different types of gas
burners, meeting all relevant requirements.
The pull-out terminal blocks allow the control device
to be easily replaced during maintenance operations.
Read and understand this manual before installing, operating, or servicing this unit. This unit must be installed
according to this manual and local regulations. The drawings may show units without covers or safety shields to
illustrate details. Disconnect power supply and follow all usual safety precautions before carrying out any operation
on the device. Be sure to reinstall covers or shields before operating any devices.
The device is not user serviceable, a faulty device must be put out of order and sent back for servicing.
CONTRIVE manufactures products used as components in a wide variety of industrial systems and equipment. The
selection and application of products remain the responsibility of the equipment manufacturer or end user.
CONTRIVE accepts no responsibility for the way its products are incorporated into the final system design. All
systems or equipment designed to incorporate a product manufactured by CONTRIVE must be supplied to the end
user with appropriate warnings and instructions as to the safe use and operation of that part.
Any warnings provided by CONTRIVE must be promptly provided to the end user.
CONTRIVE guarantees for two years from the date of manufacture of its product to replace, or, at its option, to
repair any product or part thereof (except fuses and with some limitations for tubes and photocells) which is found
defective in material or workmanship or which otherwise fails to conform to the description of its sales order.
CONTRIVE makes no warranty of merchantability or any other warranty express or implied. CONTRIVE assumes no
liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
 Gas Equipment Directive (2009/142/EC)
 Low Voltage Equipment Directive (2014/35/EC)
© 2020 CONTRIVE • B1444|FIRO.EN
SAFETY INFORMATION
CERTIFICATION
1020
AUTOMATIC BURNER CONTROL SYSTEM
 EMC Directive (2014/30/EC)
IN CONJUNCTION WITH:
EN298 – EN746-2 – EN60730-1 – EN13611
1
www.contrive.it

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FIRO and is the answer not in the manual?

Questions and answers

Summary of Contents for Contrive FIRO

  • Page 1 Any warnings provided by CONTRIVE must be promptly provided to the end user. CONTRIVE guarantees for two years from the date of manufacture of its product to replace, or, at its option, to repair any product or part thereof (except fuses and with some limitations for tubes and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of its sales order.
  • Page 2: Front Panel

    USE UNSCREENED HIGH-VOLTAGE CABLE FOR IGNITION AND IONIZATION ROD LINES, LAYING CABLES INDIVIDUALLY, AVOIDING METAL CONDUITS. KEEP HIGH VOLTAGE IGNITION CABLES AS SHORT AS POSSIBLE, AVOIDING LOOPS AND KEEP ALL OTHER CABLES, ESPECIALLY THOSE OF IONIZATION ROD, AS FAR APART AS POSSIBLE © 2020 CONTRIVE • B1444|FIRO.EN www.contrive.it 1020...
  • Page 3: Wiring Diagram

    A reset action is supposed to be a clear defined manual action. An automatic reset is not allowed by EN 13611:2015. FIRO limits the maximum number of remote resets (input terminal 4) to 5 actions within a span of 15 minutes.
  • Page 4 Configuration parameters and usage log can be retrieved also by free APP running on Android devices. Correct reception is confirmed by a green blink of LED 2. © 2020 CONTRIVE • B1444|FIRO.EN www.contrive.it 1020...
  • Page 5 4 startup attempts (including the first one), if the safety of the application is not impaired, repeating the cycle from the beginning. A lockout will occur if no flame has formed within programmed attempts. © 2020 CONTRIVE • B1444|FIRO.EN www.contrive.it 1020...
  • Page 6: Configuration Code

    Set post-purge time in forced draught burners according to standards (EN 676). The flame simulation test is carried out during this time. This is a merely waiting time if there is no air control. CONFIGURATION CODE 001 03 01 001 © 2020 CONTRIVE • B1444|FIRO.EN www.contrive.it 1020...
  • Page 7: Ignition Transformer

    The ignition transformer could be mounted inside the device or fixed on the back of the unit. TRE820 TRK2 TRK2 TRE820 EXTERNAL FITTING HOLES ASSEMBLY INSIDE EXTERNAL FITTING HOLES EXTERNAL FITTING HOLES 4.2mm SELF TAPPING SCREW WITH SILICON GLUE 4.2mm SELF TAPPING SCREW 4.2mm SELF TAPPING SCREW © 2020 CONTRIVE • B1444|FIRO.EN www.contrive.it 1020...
  • Page 8: Gas Burner

    SINGLE ROD CIRCUIT BLOWER DUAL ROD CIRCUIT LOW AIR PRESSURE SWITCH BURNER LOCKOUT RESET INPUT ALL SAFETY SWITCHES SHOULD BE APPROVED AS LIMIT CONTROLS THE USE OF ELECTRONIC SWITCHES MAY CAUSE ERRATIC OPERATIONS © 2020 CONTRIVE • B1433|FIRO.EN www.contrive.it 1020...
  • Page 9: Program Sequence

    AND ARE MENTIONED ONLY IN AN EXPLANATORY MANNER TO THE READERS’ BENEFIT, AND WITHOUT INTENTION TO INFRINGE. WHILE EVERY EFFORT HAS BEEN MADE TO MAKE SURE THE INFORMATION IN THIS DOCUMENT IS CORRECT, CONTRIVE CAN NOT BE LIABLE FOR ANY DAMAGES WHATSOEVER FOR LOSS RELATING TO THIS DOCUMENT.

Table of Contents