Laars ProtoNode FPC-N34 Startup Manual
Hide thumbs Also See for ProtoNode FPC-N34:
Table of Contents

Advertisement

Quick Links

The ProtoNode Start-up Guide
Document 4236K
ProtoNode FPC-N34 and ProtoNode FPC-N35
Start-up Guide
Start-up Guide
For Interfacing LAARS Products:
Sola, Multiburner, SV2, HTD, OmniTherm, MagnaTherm
ProtoNode FPC-N34 and ProtoNode FPC-N35
To Building Automation Systems:
For Interfacing LAARS Products
BACnet MS/TP, BACnet/IP, Modbus TCP/IP, Metasys N2, LonWorks and
SMC Cloud
APPLICABILITY & EFFECTIVITY
Explains ProtoNode hardware and how to install it.
The instructions are effective for the above as of October 2020.
Document Revision: 14.A
Web Configurator
Document Revision: 14.B
Template Revision: 72
Web Configurator
800.900.9276 • Fax 800.559.1583
800.900.9276 • Fax 800.559.1583
Customer Service and Product Support:
(Customer Service, Service Advisors)
LAARS ProtoNode Start-up Guide
0
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
20
Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
Headquarters:
(Applications Engineering)
MSAsafety.com
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
9 Brigden Gate, Halton Hills, Ontario, Canada L7G 0A3 • 905.203.0600 • Fax 905.636.0666
www.Laars.com
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 21-05 Document 4236K

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProtoNode FPC-N34 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Laars ProtoNode FPC-N34

  • Page 1 MSAsafety.com 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130 9 Brigden Gate, Halton Hills, Ontario, Canada L7G 0A3 • 905.203.0600 • Fax 905.636.0666 www.Laars.com www.Laars.com Litho in U.S.A. © Laars Heating Systems 21-05 Document 4236K...
  • Page 2 Thank you for purchasing the ProtoNode for LAARS. Please call LAARS for technical support of the ProtoNode product. MSA Safety does not provide direct support. If LAARS needs to escalate the concern, they will contact MSA Safety for assistance. Support Contact Information:...
  • Page 3 (Section 3.2) 4. If using a serial field protocol: Connect the ProtoNode FPC-N34 3 pin RS-485 port to the field protocol cabling, (Section 3.3) or connect the ProtoNode FPC-N35 2 pin LonWorks port to the field protocol cabling. (Section 3.4) 5.
  • Page 4: Table Of Contents

    2.3.2 Set Node-ID for Any Device Attached to the ProtoNode ............11 Interfacing ProtoNode to Devices ....................12 ProtoNode FPC-N34 and FPC-N35 Showing Connection Ports ..........12 Serial Device Connections to the ProtoNode ................. 13 3.2.1 Biasing the RS-485 Device Network ..................14 3.2.2...
  • Page 5 11.6 SMC Cloud Connection Warning Message ................62 11.7 System Status Button ......................63 11.8 Routing Settings ........................64 Vendor Information – LAARS ......................65 Specifications ..........................66 13.1 Compliance with UL Regulations.................... 66 Limited 2 Year Warranty ........................ 67...
  • Page 6 Figure 3: Points per Device ..........................10 Figure 4: COM Settings ............................11 Figure 5: ProtoNode FPC-N34 (Top) and ProtoNode FPC-N35 (Bottom) ............12 Figure 6: Device and Power Connections ......................13 Figure 7: RS-485 Biasing Switch on the ProtoNode N34 (Left) and ProtoNode N35 (Right) ......14 Figure 8: RS-485 End-Of-Line Termination Switch on the ProtoNode N34 (Left) and ........
  • Page 7 Figure 62: FieldServer Password Update via FS-GUI ..................61 Figure 63: SMC Cloud Connection Problems Message ..................62 Figure 64: Routing Settings ..........................64 Figure 65: Specifications ............................. 66 LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 8: Introduction

    ProtoNode Gateway The ProtoNode is an external, high performance building automation multi-protocol gateway that is preconfigured to automatically communicate between LAARS’ devices (hereafter simply called “device”) connected to the ProtoNode and automatically configures them for BACnet MS/TP, BACnet/IP, Modbus ®1 TCP/IP or LonWorks It is not necessary to download any configuration files to support the required applications.
  • Page 9 Generate diagnostic captures (as needed for troubleshooting) without going to the site. For more information about the SMC Cloud, refer to the SMC Cloud Start-up Guide. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 10: Setup For Protonode

    Total Registers FPC-N34-0701 1,500 FPC-N35-0702 1,500 Figure 2: Supported Point Count Capacity Devices Point Count Per Device Sola Multiburner OmniTherm MagnaTherm Figure 3: Points per Device LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 11: Configuring Device Communications

    Instance for BACnet/IP and BACnet MS/TP. (Section 8.5) NOTE: The Modbus TCP/IP field protocol Node-ID is automatically set to be the same value as the Node-ID of the device. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 12: Interfacing Protonode To Devices

    LAARS Heating Systems Page 12 of 72 Interfacing ProtoNode to Devices ProtoNode FPC-N34 and FPC-N35 Showing Connection Ports Figure 5: ProtoNode FPC-N34 (Top) and ProtoNode FPC-N35 (Bottom) LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 13: Serial Device Connections To The Protonode

    Serial Device Connections to the ProtoNode ProtoNode 6 Pin Phoenix connector: • The 6 pin Phoenix connector is the same for ProtoNode FPC-N34 and FPC-N35 (LonWorks). • Pins 1 through 3 are for RS-485 devices. Use standard grounding principles for RS-485 GND •...
  • Page 14: Biasing The Rs-485 Device Network

    To turn biasing ON, move the 2 red biasing jumpers to straddle the 4 pins closest to the inside of the board of the ProtoNode. RS-485 Bias Switch (off) Figure 7: RS-485 Biasing Switch on the ProtoNode N34 (Left) and ProtoNode N35 (Right) LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 15: End Of Line Termination Switch For The Rs-485 Device Network

    Always leave the single red jumper in the A position (default factory setting). RS-485 EOL Switch (off) Leave in Position A Figure 8: RS-485 End-Of-Line Termination Switch on the ProtoNode N34 (Left) and ProtoNode N35 (Right) LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 16: Serial Network (Fpc-N34): Wiring Field Port To Rs-485 Network

    To enable biasing, turn the bias switch ON (switch position = left side) NOTE: Biasing only needs to be enabled on one device. The ProtoNode has 510 ohm resistors that are used to set the biasing. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 17: Lonworks (Fpc-N35): Wiring Lonworks Devices To The Lonworks Terminal

    Wire the LonWorks device network to the ProtoNode LonWorks Terminal. Use approved cable per the FT-10 installation guidelines LonWorks has no polarity. Figure 11: LonWorks Terminal LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 18: Power-Up Protonode

    ProtoNode ProtoNode Pin # Assignment Power In (+) Pin 4 Power In (-) Pin 5 Frame Ground Pin 6 FRAME GND Figure 13: Power Connections LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 19: Connect The Pc To The Protonode

    Select and enter a static IP Address on the same subnet. For example: • Click the Okay button to close the Internet Protocol window and the Close button to close the Ethernet Properties window. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 20: Setup Web Server Security

    When the warning that “Your connection is not private” appears, click the advanced button on the bottom left corner of the screen. Figure 16: Connection Not Private Warning LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 21: Figure 17: Warning Expanded Text

    NOTE: A user has 5 attempts to login then there will be a 10-minute lockout. There is no timeout on the FieldServer to enter a password. NOTE: To create individual user logins, go to Section 11.5. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 22: Select The Security Mode

    NOTE: Cookies are used for authentication. NOTE: To change the web server security mode after initial setup, go to Section 11.1. The sections that follow include instructions for assigning the different security modes. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 23: Https With Own Trusted Tls Certificate

    • Select one of these options and click the Save button. • A “Redirecting” message will appear. After a short time, the FieldServer GUI will open. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 24: Configure Network Settings

    A warning message will appear when performing the first-time setup, click the Exit Registration button to continue to the Network Settings page. Figure 23: FS-GUI Landing Page LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 25: Change The Protonode Ip Address

    NOTE: If the webpage was open in a browser, the browser will need to be pointed to the new IP Address of the ProtoNode before the webpage will be accessible again. Figure 24: Ethernet Port Network Settings NOTE: For Router settings go to Section 11.8. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 26: Smc Cloud User Setup, Registration And Login

    NOTE: If a warning message appears instead, go to Section 11.6 to resolve the connection issue. Figure 25: Generic Web App Page – First Login LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 27: Figure 26: Smc Cloud Opt Out Warning Window

    NOTE: If SMC Cloud integration with the ProtoNode is not desired, skip to Section to continue gateway setup. If user setup is already complete go to Section 7.3. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 28: User Setup

    Figure 27: Welcome to SMC Cloud Email NOTE: If no SMC Cloud email was received, check the spam/junk folder for an email from notification@fieldpop.io. Contact the manufacturer’s support team if no email is found. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 29: Figure 28: Setting User Details

    Click “Save” to save the user details. • Click “OK” when the Success message appears. • Record the email account used and password for future use. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 30: Registration Process

    Figure 29: SMC Cloud Registration Message • Click Get Started to view the SMC Cloud registration page. NOTE: For information on the System Status button, go to Section 11.7. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 31: Figure 30: Smc Cloud Registration - Installer Details

    Figure 30: SMC Cloud Registration – Installer Details Enter the site details by entering the physical address fields or the latitude and longitude then click Next Figure 31: SMC Cloud Registration – Site Details LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 32: Figure 32: Smc Cloud Registration - Gateway Details

    Enter Name and Description (required) then click Next Figure 32: SMC Cloud Registration – Gateway Details Enter user credentials and click Register Device Figure 33: SMC Cloud Registration – SMC Cloud Account LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 33: Figure 34: Device Registered For Smc Cloud

    Figure 34: Device Registered for SMC Cloud NOTE: Update these details at any time by going to the SMC Cloud™ tab and clicking the Update Device Details button. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 34: Login To Smc Cloud

    On first login, the Privacy Policy window will appear. Read the Terms of Service, click the checkbox to accept the terms and then click the Continue button to access SMC Cloud. Figure 36: SMC Cloud Privacy Policy LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 35: Figure 37: Smc Cloud Landing Page

    The ProtoNode Start-up Guide Page 35 of 72 NOTE: For additional SMC Cloud instructions see the SMC Cloud Start-up Guide. Figure 37: SMC Cloud Landing Page LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 36: Configure The Protonode

    Figure 39: Configure Tab NOTE: For Web App instructions to the System View, Data Log Viewer, Event Logger and Virtual Points functions, see the SMC Cloud Start-up Guide. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 37: Select Field Protocol And Set Configuration Parameters

    Parameter Description in parentheses. NOTE: If multiple devices are connected to the ProtoNode, set the BACnet Virtual Server Nodes field to “Yes”; otherwise leave the field on the default “No” setting. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 38: Setting Protonode Active Profiles

    Active Profiles section lists the currently active device profiles, including previous Web Configurator additions. This list is empty for new installations, or after clearing all configurations. (Figure Figure 41: Web Configurator Showing no Active Profiles LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 39: Verify Device Communications

    Check that the port TX1 and RX1 LEDs are rapidly flashing. See Section 10.4 for additional LED information and images. • Confirm the software shows good communications without errors (Section 10.2). LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 40: Bacnet: Setting Node_Offset To Assign Specific Device Instances

    Device 3 Instance = 50,000 + Node_ID = 50,000 + 33 = 50,033 • Click “Submit” once the desired value is entered. Figure 44: Web Configurator Node Offset Field Figure 45: Active Profiles LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 41: How To Start The Installation Over: Clearing Profiles

    At the bottom-left of the page, click the “Clear Profiles and Restart” button. • Once restart is complete, all past profiles discovered and/or added via Web configurator are deleted. The unit can now be reinstalled. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 42: Lonworks (Fpc-N35): Commissioning Protonode On A Lonworks Network

    Select and enter a static IP Address on the same subnet. For example: • Click the Okay button to close the Internet Protocol window and the Close button to close the Ethernet Properties window. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 43: Figure 47: Sample Of Fserver.xif File Generated

    If the web browser prompts to save the file, save the file onto the PC. If the web browser displays the xif file as a web page, save the file onto the local PC as “fserver.xif”. Figure 47: Sample of Fserver.XIF File Generated LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 44: Troubleshooting

    • Double click on the FS Toolbox Utility and click Discover Now on the splash page. • Check for the IP Address of the desired gateway. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 45: Viewing Diagnostic Information

    If there are any errors showing on the Connection page, refer to Section 10.3 for the relevant wiring and settings. Figure 49: Error Messages Screen LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 46: Checking Wiring And Settings

    Visual observations of LEDs on the ProtoNode (Section 10.4) Verify IP Address setting Verify wiring NOTE: If the problem persists, a Diagnostic Capture needs to be taken and sent to support. (Section 10.5) LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 47: Led Diagnostics For Communications Between Protonode And Devices

    The ProtoNode Start-up Guide Page 47 of 72 10.4 LED Diagnostics for Communications Between ProtoNode and Devices See the diagram below for ProtoNode FPC-N34 and FPC-N35 LED Locations. Diagnostic LEDs Description The SPL LED will light if the unit is not getting a response from one or more of the configured devices.
  • Page 48: Taking A Fieldserver Diagnostic Capture

    Email the diagnostic zip file to technical support. NOTE: Diagnostic captures of BACnet MS/TP communication are output in a “.PCAP” file extension which is compatible with Wireshark. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 49: Taking A Capture With Older Firmware

    Connect a standard Cat-5 Ethernet cable between the PC and ProtoNode. • Double click on the FS Toolbox Utility. • Step 1: Take a Log Click on the diagnose icon for the desired device LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 50 Once the diagnostic test is complete, a .zip file is saved on the PC Choose “Open” to launch explorer and have it point directly at the correct folder Send the Diagnostic zip file to technical support LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 51: Factory Reset Instructions

    NOTE: Internet Explorer is no longer supported as recommended by Microsoft. NOTE: Computer and network firewalls must be opened for Port 80 to allow FieldServer GUI to function. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 52: Additional Information

    Go to www.BACnetInternational.net for more information about the BACnet Testing Laboratory. Click here for the BACnet PIC Statement. NOTE: BACnet is a registered trademark of ASHRAE. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 53: Lonmark Certification

    MSA Safety has more LonMark Certified gateways than any other gateway manufacturer, including the ProtoCessor, ProtoCarrier and ProtoNode for OEM applications and the full featured, configurable gateways. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 54: Change Web Server Security Settings After Initial Setup

    NOTE: Any changes will require a FieldServer reboot to take effect. • From the FS-GUI page, click Setup in the Navigation panel. Figure 53: FS-GUI Page LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 55: Change Security Mode

    Figure 54: FS-GUI Security Setup • Click the Mode desired. If HTTPS with own trusted TLS certificate is selected, follow instructions in Section 5.2.1 • Click the Save button. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 56: Edit The Certificate Loaded Onto The Fieldserver

    Click the Edit Certificate button to open the certificate and key fields. • Edit the loaded certificate or key text as needed. • Click Save. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 57: Change User Management Settings

    Admin – Can modify and view any settings on the FieldServer. Operator – Can modify and view any data in the FieldServer array(s). Viewer – Can only view settings/readings on the FieldServer. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 58: Create Users

    Password text field. • Click the Create button. • Once the Success message appears, click OK. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 59: Edit Users

    Once the User Edit window opens, change the User Security Group and Password as needed. Figure 59: Edit User Window • Click Confirm. • Once the Success message appears, click OK. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...
  • Page 60: Delete Users

    Click the trash can icon next to the desired user to delete the entry. Figure 60: Setup Users • When the warning message appears, click Confirm. Figure 61: User Delete Warning LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 61: Change Fieldserver Password

    NOTE: The password must meet the minimum complexity requirements. An algorithm automatically checks the password entered and notes the level of strength on the top right of the Password text field. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 62: Smc Cloud Connection Warning Message

    FieldServer by clicking on the Confirm button in the window and click on the bolded “Restart” text in the yellow pop-up box that appears in the upper right corner of the screen. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 63: System Status Button

    26), the SMC Cloud status will not show in the System Status window. This means the status will show as green even if the gateway is not connected to SMC Cloud. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 64: Routing Settings

    Set the Priority for each connection (1-255 with 1 as the highest priority and 255 as the lowest). • Click the Save button to activate the new settings. Figure 64: Routing Settings LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com •...
  • Page 65: Vendor Information - Laars

    Page 65 of 72 12 Vendor Information – LAARS See the document “LAARS Vendor Mappings” for the complete point list for all the devices referenced in this manual. Only the protocols listed as supported for this FieldServer are supported (see Section 1.1).
  • Page 66: Specifications

    Restricted Access Area requiring a key or a special tool to gain access. • This device must not be connected to a LAN segment with outdoor wiring. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 67: Limited 2 Year Warranty

    MSA Safety for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product. LAARS ProtoNode Start-up Guide Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com...
  • Page 68 The ProtoNode Start-up Guide Notes: Industrial Way, Rochester, NH, USA 03867 (800) 900-9276 www.Laars.com • •...