LG ARND30UDBE4 Installation Manual page 41

Table of Contents

Advertisement

ROUTINE MAINTENANCE
DANGER
Electric shock hazard. Can cause injury or death. Before
attempting to perform any service or maintenance, turn
the electrical power to the unit to OFF).
CAUTION
Use caution when removing access panels or other unit
components, especially while standing on a ladder or
other potentially unsteady base. Access panels and unit
components can be heavy and serious injury may occur
This unit requires minimal maintenance to operate
properly. Maintenance requirements for this model vary
for each installation and depend greatly on how much
the system is used and the cleanliness of the air.
Proper maintenance will both increase the life of the
system and maintain its efficiency. Maintenance must be
performed by experienced technicians and in the case of
refrigeration systems, must be done by an EPA certified
technician.
Maintenance frequency is based on a presumed
nominal use of the system. If the system is being run
constantly, the frequency should be adjusted
accordingly. If there is seasonal debris in the air which
can be drawn into the filters and the coils, they should
be checked more frequently. If the system is being used
for only a few hours per day, the frequency may be
reduced. Use the maintenance log at the end of this
manual to record each maintenance session and
observations and then establish a maintenance
schedule that is appropriate for the installation. The
following is provided as a guideline.
Maintenance Frequency:
Monthly
1. External Filter
Clean Aluminum mesh filters
2. Internal Filters
Replace MERV 8 filters monthly. Adjust replacement
schedule for MERV 13 and MERV 14 or other filters
as inspection requires
Semiannually
.
1. Check motor and motor bearings
Check for excessive heat, vibration or noise.
2. Condensate
Drain Inspect and Clean (Refill with water)
3. Coils Inspect for cleanliness
Clean as required
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Due to our policy of continuous product innovation, some specifications may change without notification.
Annually
It is recommended that the annual inspection and
maintenance occur at the start of the cooling season.
1. Dampers
Check for unobstructed operation
2. Blower Wheel and Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
3. Door Seal Check if intact and pliable
4. Wiring Connections
Check all connections for tightness
5. Cabinet
Check entire cabinet, inside and out, for dirt buildup
or corrosion.
Remove accumulated dirt, remove any surface
corrosion and coat the area with appropriate finish.
41

Advertisement

Table of Contents
loading

Table of Contents