Omega HEC-12
Quick Response
Horizontal Sidewall Sprinkler
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product
Description
The Omega Model HEC-12
sprinkler is an extremely versatile
horizontal sidewall sprinkler. It is a
low profile, aesthetically pleasing,
wall mounted sprinkler that operates
five to six times faster than a
standard sprinkler. It offers a high
degree of protection for human life
and features a spray pattern that has
been shown to be effective in the
control or extinguishment of fire.
The Model HEC-12 carries a
Listing* by Underwriters Laboratories
for use as a Quick Response
Sprinkler that is listed for installation
in light hazard and ordinary hazard
occupancies in accordance with
current NFPA 13 Standards.
The Model HEC-12 is available in
three standard finishes, chrome
plated, brass plated and white
painted. Its mating escutcheon plate
is available in three standard finishes,
chrome plated, brass plated and
white painted, with additional special
finishes available upon request.
Operation: A fusible alloy pellet is
compressed with a bearing disc into a
copper housing by a ball plunger.
Heat is absorbed by the heat
collecting fins and conducted to the
alloy pellet. At the rated temperature
the alloy melts, causing the ball
plunger to drop, freeing balls from the
retaining groove. This movement
allows system water pressure to force
* For specific listing requirements see the appropriate
information contained in this brochure.
the orifice sealing mechanism and
deflector assembly open. Water is
then discharged in a designed flow
pattern.
Technical
Data
Model: HEC-12
Style:
Horizontal Sidewall
Orifice Size: 1/2"
(12.7 mm)
K Factor: 5.6
(80.08)
Thread Size: 1/2" N.P.T.
Temperature Rating: 145°F/63°C
160°F/71°C
200°F/93°C
Approvals: U.L., U.L.C., M.E.A.
(Cal. No. 375-75-SA)
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes:
Sprinkler: chrome plated, brass
plated and white
painted
Escutcheon: chrome plated, brass
plated and white
painted
Length: 2 3/8"
(60.33 mm)
Width: 1 3/8"
(34.9 mm)
Weight: 4.5 oz.
(127.6 grams)
HEC-12 8-92
1⁄2" Orifice
Horizontal
Sidewall
Automatic
Sprinkler
No. 1-5.0

Advertisement

loading
Need help?

Need help?

Do you have a question about the CENTRAL Omega HEC-12 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco Fire Product CENTRAL Omega HEC-12

  • Page 1 HEC-12 8-92 Omega HEC-12 Quick Response Horizontal Sidewall Sprinkler Manufactured by: Central Sprinkler Company 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 1⁄2" Orifice Product the orifice sealing mechanism and deflector assembly open. Water is Description then discharged in a designed flow Horizontal pattern.
  • Page 2 Installation Diagram Omega HEC-12 Horizontal Sidewall Sprinkler Finished Wall Line Finished Ceiling Line 1" x 1/2" Reducing 4" to 12" Coupling (N.P.T.) 1/2" Escutcheon 5/8" 1" Supply Pipe ±1/8" Note: Use this flange for field 1"±1/8" installation. Use Central's Omega Sidewall Sprinkler Wrench.
  • Page 3 Special care must be taken when Design installing with a copper system. Sprinklers must be installed only after Data the inside of the sprinkler nipple and associated fittings have been wire brushed to remove any flux. Residual Design Requirements — Quick Response Applications flux can cause corrosion and in extreme cases can impair proper In Quick Response applications, Model HEC-12 145°F, 160°F and 200°F rated...
  • Page 4 Because the discharge pattern is Ordering critical to protection of life and property, nothing should be hung or Information attached to the sprinkler unit that would disrupt the pattern. Such obstructions must be removed. In the When placing an order, indicate the event that construction has altered full product name.