Hydro Unit Installation; Positioning; Refrigerant Piping - Toshiba HWT-601XWHM3W-E Installation Manual

Air to water heat pump, hydro unit wall mounted type
Hide thumbs Also See for HWT-601XWHM3W-E:
Table of Contents

Advertisement

Hydro Unit
7
Hydro Unit
installation
WARNING
WARNING
• To protect yourself from injury, always use PPE
(Personal Protective Equipment), that is, wear gloves.
• Install the Hydro Unit by at least two persons.
• Install the Hydro Unit in a place strong enough to
withstand the following weights:
The dry weight of the Hydro Units is displayed on the
product nameplate. When the Hydro Unit, is filled with
water the weight of the unit will increase by 12 kg.
CAUTION
• Do not install the unit in a place where water freezes.
• Do not install the Hydro Unit in a place where
combustible gas may leak.
• Do not install the Hydro Unit in a place exposed to rain
or water.
• Do not install the Hydro Unit near equipment which
generates heat.
• Do not install the Hydro Unit to a movable object.
• Do not install the Hydro Unit in a place exposed to
vibration.
• The unit must be installed in accordance with national
wiring regulation.
• The Hydro Unit must not be installed in a high humidity
condition area.
Handling, unpacking, and
checking the Hydro Unit
• The unit should be checked when it is delivered, and
any damage reported immediately to the courier
claims department.
15-EN

Positioning

Service space
Secure a service space for the Hydro Unit.
• Do not install the Hydro Unit in a place where heat
stagnates.
▼Fig.7-01
250 mm
500 mm
250 mm
250 mm
500 mm
Mounting
Install M8 bolts at the positions shown below and
secure them with nuts.
NOTE
If customer worried about vibration of Hydro Unit,
please insert vibration isolating material between the
product and the wall, when installing the product.
The back side of the Hydro Unit can be highly heated,
therefore, the installing surface must be heat-resistant.
▼Fig.7-02
▼Fig.7-03
380
Secure the Hydro Unit with
plain washers and nuts.
Install the Hydro Unit so that its tilting angle falls within
the range below.
▼Fig.7-04
▼Fig.7-05
± 1°
– 8 –

Refrigerant piping

WARNING
WARNING
• THIS SYSTEM ADOPTS HFC REFRIGERANT (R32)
WHICH DOES NOT DESTROY THE OZONE LAYER.
M8
• Therefore during installation work prevention of the
invasion of water, dust, former refrigerant or oil is of a
paramount importance.
To prevent the charging of incorrect refrigerants into
the system the service valve connection ports have
also increased in size.
• The use of R32 or R410A tools is required for correct
installation of the system.
• The use of the correct pipe sizes and wall thicknesses
of copper pipe work is required for the correct
installation of the system.
CAUTION
• Ensure all refrigerant pipes are protected from the
invasion of dust and water.
• Ensure all pipe work connections are tightened to the
required torque settings detailed in this section.
• Perform an air tight test using Oxygen Free Nitrogen
± 1°
(OFN) only.
• Evacuate the air in the pipe work using a vacuum
pump.
• Check for refrigerant gas leaks at all connections
throughout the pipe work.
NOTE
The Air to Water Heat Pump System uses R32
refrigerant. It is important that copper pipes used for
refrigerant piping have the following wall thickness:
• 0.8 mm for Ø6.4 mm and Ø12.7 mm
• 1.0 mm for Ø15.9 mm
Installation Manual
16-EN