Installation Instructions
Step 3 - Installation of the Outdoor Unit (Cont.)
• The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland
waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland
waterways, please follow the installation instruction below.
• Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which
can damage the outdoor unit.
Sea breeze
Sea
• If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the
sea breeze.
• A protection wall should be constructed with a solid material to block the sea
breeze. The height and the width of the wall should be 1.5 times larger than
the size of the outdoor unit. Also, allow at least 28" (700mm) between the
protection wall and the outdoor unit for air circulation to ventilate.
• Install the outdoor unit in a place where water can drain freely.
• If the above conditions cannot be met, contact GE Appliances for assistance.

Explaining Operation To the End User

• Using the Owner's Manual, explain to the user
how to use the heat pump, (the remote controller,
adding/removing the air filters, placing or
removing the remote controller from the remote
control holder, cleaning methods, precautions for
operation, etc.)
• Review precautions for operation.
• Recommend that the user read the Operating
Instructions carefully.
31-5000276 Rev. 1
ODU
ODU

Step 4 - Final Check

Sea breeze
Sea
Sea
Check Items for Test Run
No gas leak from linesets?
Are the linesets insulated properly?
Are the connecting wirings of indoor and outdoor
firmly inserted to the terminal block?
Is the connecting wiring of indoor and outdoor
fixed?
Is condensate draining correctly?
Is the ground wire securely connected? Is the
indoor unit securely fixed?
Is power source voltage correct according to local
code?
Is there any odd noise?
Does the cooling temperature drop between
20-30°F?
Does the heating temperature raise between
35-40°F?
Is the room temperature display accurate?
ODU
Protection walls
Sea breeze
ODU
ODU
13