Datalogic PWR-120 Installation Manual
Hide thumbs Also See for PWR-120:

Advertisement

Quick Links

> PWR-120

Advertisement

Table of Contents
loading

Summary of Contents for Datalogic PWR-120

  • Page 1 > PWR-120...
  • Page 2 PWR-120 Installation Manual Ed.: 12/2018 © 2002 – 2018 Datalogic S.p.A. and/or its affiliates  ALL RIGHTS RESERVED.  Without limiting the rights under copyright, no part of this documentation may be reproduced, stored in or introduced into a retrieval system, or transmitted in any form or by any means, or for any purpose, without the express written permission of Datalogic S.p.A.
  • Page 3: Table Of Contents

    4.4.1 Supply Capacity When Wiring to XRF410N Readers ..........10 4.4.2 Supply Capacity When Wiring to Matrix 450N Readers ..........12 AC LINE VOLTAGE ELECTRICAL CONNECTIONS ..........13 AC Line Input Voltage ....................13 TECHNICAL FEATURES ..................14 ELECTRICAL DIAGRAMS ..................15 PWR-120 Electrical Diagram ..................15...
  • Page 4: Safety Regulations

    SAFETY REGULATIONS ELECTRICAL SAFETY This product conforms to the applicable requirements contained in the following European Standards: • EN 61439-1 • EN 60204-1 • EN 60950-1 +A11 +A1 +A12 +A2 IMPORTANT: This symbol is used to bring the user’s attention to details that are considered IMPORTANT.
  • Page 5: Ce Compliance

    SUPPORT THROUGH THE WEBSITE Datalogic provides several services as well as technical support through its website. Log on to www.datalogic.com and click on the SUPPORT link which gives you access to: •...
  • Page 6: General View

    GENERAL VIEW Key Lock Thermal-Magnetic Circuit Breaker Product Data Label AC Line Input Terminal Block “DC OK” Terminal Block Compression Connectors AS-I Cable Sealing Grommet 24 Vdc Terminal Block Monophase Switching Power Supply Figure 2 – PWR-120 General View...
  • Page 7: Operating Features

    1 OPERATING FEATURES 1.1 DESCRIPTION The PWR-120 is an electrical cabinet housing a 24 Vdc power supply which is used to power up a varying number of reading devices (depending on the product), along with their relative accessory devices. See chapter 4 for details.
  • Page 8 PWR-120 INSTALLATION MANUAL Example 2: 125% power overload The overload is supplied for approximately 10 seconds and then is reduced (Voltage and Current) to about 95% power for another 10 seconds. In this case the output voltage falls below 20 Vdc and therefore the power supply shuts down for a recovery time of 17 seconds. This procedure is repeated until the excessive current overload is resolved.
  • Page 9: Pre-Installation Checklist

    PRE-INSTALLATION CHECKLIST 2 PRE-INSTALLATION CHECKLIST This chapter can be used as a checklist to verify all the steps necessary to complete installation of the PWR power Supply. CAUTION: Opening the cabinet requires a key that should be used by a person adequately advised or supervised by an electrically skilled person to enable him or her to perceive risks and avoid hazards which electricity can create.
  • Page 10: System Wiring: Test

    PWR powers up correctly. The green DC-OK light should be on steady and the overload light (red) should off. Close and lock the PWR enclosure and check that it does not open (lock functions correctly). The PWR-120 installation is now complete.
  • Page 11: Mechanical Installation

    IMPORTANT: The cabinet must be installed vertically in such a way that the key lock is no higher than 1.90 m from the ground (see Fig. 2). Figure 7 – PWR-120 cabinet max. height Please note that the cabinet door can be unlocked and opened by using the key provided along...
  • Page 12: Low Voltage Electrical Connections

    Compression Connectors Follow these instructions to correctly insert the cables: Determine the number and size of the cables coming into and leaving the PWR-120. Locate the correct compression connector sizes and positions relative to these cables. Pass the cable end through the proper compression connector so that the gland material seals around it when tightened.
  • Page 13: Dc Voltage Terminal Block

    LOW VOLTAGE ELECTRICAL CONNECTIONS 4.2 DC VOLTAGE TERMINAL BLOCK DC OK signals DC Outputs Figure 9 – PWR-120 DC Output Power Connections 4.2.1 DC OK Monitoring The DC voltage terminal block provides two wiring terminals (13-14), which monitor the status of the switching power supply (DC OK feature).
  • Page 14: Laser Barcode Scanners

    The power supply unit is connected directly to the scanners via AS-I cabling. AC in 24 Vdc to scanners using AS-I cabling with end cap Figure 10 - Connecting PWR-120 to AS-I Compatible Scanners Refer to the specific scanner manual for I/O interface wiring connections.
  • Page 15: Supply Capacity When Wiring Directly To Lonworks Scanners

    See the specific scanner manual for consumption data. The maximum number of scanners to be supplied for direct wiring by a single PWR-120 is shown in the table below:...
  • Page 16: Image-Based Id Readers

    PWR-120 INSTALLATION MANUAL 4.4 IMAGE-BASED ID READERS 4.4.1 Supply Capacity When Wiring to XRF410N Readers The maximum number of XRF410N modules to be supplied by a single PWR-120 is shown in the following table. Maximum Number of Modules XRF410N Model...
  • Page 17 Master AC in Terminator Custom Cable CBL-1480-05 CBX500 ATS-001 CAB-DS05-S P.S. Ethernet Host Figure 13 - Connecting PWR-120 to an XRF410N Hi Perf Module Custom Power Cable to CBX CAB-MLP-0x Cable PWR-120 Wire Color Meaning 24 V+ White 24 V+...
  • Page 18: Supply Capacity When Wiring To Matrix 450N Readers

    The Matrix M450N uses the CAB-LD-102 no power cable CAB-MS0x between the reader and its relative LT-03x illuminator. Figure 14 - Connecting PWR-120 to a Matrix 450N Custom Power Cable to CBX CAB-LP-0x Cable to LT-03x PWR-120 Wire Color Meaning...
  • Page 19: Ac Line Voltage Electrical Connections

    PWR-120 input components are rated for an Icp of 10 kA max. Wiring methods from the branch circuit breaker to the PWR-120 power supply shall comply with the National Electric Code ANSI\NFPA. The Datalogic DWS-SWITCH is an AC Power Disconnector and Distributor cabinet which provides this protection.
  • Page 20: Technical Features

    PWR-120 INSTALLATION MANUAL 6 TECHNICAL FEATURES ELECTRICAL FEATURES Input Voltage AC from 100 to 240 V from 50 to 60 Hz Input Current Consumption Max 6 A Icp 10kA - output at full load Output Voltage 24 Vdc Nominal Output Current Max Continuous Overcurrent 5.5 A (up to 40°...
  • Page 21: Aelectrical Diagrams

    ELECTRICAL DIAGRAMS ELECTRICAL DIAGRAMS PWR-120 ELECTRICAL DIAGRAM The PWR-120 components are electrically connected as displayed in the following diagram: Figure 16 - PWR-120 Electrical Diagram...