Installation Procedure
Step 1 Checking and preparing
accessories
The following accessories are supplied with the indoor
unit. The type and quantity may differ, depending on the
specifications.
Pattern sheet (1)
Insulation pipe
(Liquid side1, gas side1)
Installation manual (1)
Cable-tie (6)
Drain hose (1)
Insulation drain hose (1)
User manual (1)
Clamp (1)
Step 2 Choosing the installation
location
WARNING
• Because your air conditioner contains R-32 refrigerant,
make sure that it is installed, operated, and stored it
in a room whose floor area is larger than the minimum
required floor area specified in the following table:
Ceiling-mounted type
m (kg)
≤ 1.842
1.843
1.9
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.6
3.8
4.0
4.2
4.4
4.6
4.8
5.0
- m : Total refrigerant charge in the system
- A : Minimum required floor area
• IMPORTANT: it's mandatory to consider either the
table above or taking into consideration the local
law regarding the minimum living space of the
premises.
• Minimum installation height of indoor unit is 0.6 m
for floor mounted, 1.8 m for wall, 2.2 m for ceiling.
Installation location requirements
• There must be no obstacles near the air inlet and
outlet.
• Install the indoor unit on a ceiling that can support its
weight.
A (m²)
No requirement
3.64
3.75
3.95
4.34
4.74
5.13
5.53
5.92
6.48
7.32
8.20
9.14
10.1
11.2
12.3
13.4
14.6
15.8
5
English