Full stainless steel units and units protected by the Baltibond
hybrid coating do not require passivation.
An exception to this are units with a galvanized steel coil bundle which do still require the proper
passivation procedure as described here in this section.
In case you can't keep the pH below 8.2, a secondary approach is to conduct a chemical passivation using
inorganic phosphate or film-forming passivation agents. Consult your water treatment specialist for specific
recommendation.
15
3 Water Care
3 Water Care