BAC FXVT 288 Series Operating And Maintenance Instructions Manual page 12

Closed circuit cooling towers
Table of Contents

Advertisement

pH
pH during initial passivation
Total hardness (as CaCO
Total alkalinity (as CaCO
Total dissolved solids
Conductivity
Chlorides
Sulfates*
Total suspended solids
Chlorination (as free chlorine / halogen): continuous
Chlorination (as free chlorine / halogen): batch dosing for cleaning &
disinfection
*Note: Higher concentration of sulfates is allowed, provided the sum of chlorides + sulfates parameters does not exceed 650 mg/l for
Baltibond/SST304L.
pH
pH during initial passivation
Total hardness (as CaCO
Total alkalinity (as CaCO
Total dissolved solids
Conductivity
Chlorides
Sulfates*
Total suspended solids
Chlorination (as free chlorine / halogen): continuous
Chlorination (as free chlorine / halogan): batch dosing for cleaning &
disinfection
*Note: Higher concentration of sulfates is allowed provided the sum of chlorides + sulfates parameters does not exceed 500 mg/l for Baltiplus
protection.
12
W W W . B A L T I M O R E A I R C O I L . E U
)
3
)
3
Circulated water quality guidelines for Baltibond
)
3
)
3
Circulated water quality guidelines for Baltiplus protection
®
Baltibond
Hybrid Coating and SST304L
6.5 to 9.2
Below 8.2
(for units with HDG coil only)
50 to 750 mg/l
600 mg/l max.
2050 mg/l max.
3300 µS/cm
300 mg/l max.
350 mg/l max.*
25 mg/l max.
1.5 mg/l max.
5-15 mg/l max. for 6 hours max.
25 mg/l max. for 2 hours max.
50 mg/l max. for 1 hour max.
®
Hybrid Coating
Baltiplus protection
6.5 to 9.0
Below 8.2
50 to 600 mg/l
500 mg/l max.
1500 mg/l max.
2400 µS/cm
250 mg/l max.
250 mg/l max.*
25 mg/l max.
1 mg/l max.
5-15 mg/l max. for 6 hours max.
25 mg/l max. for 2 hours max.
50 mg/l max. for 1 hour max.