LG LT-H182QLE0 Installation Manual page 10

Ceiling cassette
Table of Contents

Advertisement

Installation
Ceiling opening dimensions and hanging bolt location
• The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.
• Please use included paper or cardboard on the bottom of packaging as installation paper
• Select and mark the position for fixing bolts and pip-
ing hole.
• Decide the position for fixing bolts slightly tilted to
the drain direction after considering the direction of
drain hose.
• Drill the hole for anchor bolt on the ceiling.
• The hole size for four anchor bolts is
Ø 14.5mm & 40mm depth.
• When using cardboard on the bottom of packaging,
use after separating installation paper from bottom
of the product packaging using back of a knife as
shown in the picture (TM/TN/TP)
CAUTION:
• This air-conditioner uses a drain pump.
• Horizontly install the unit using a level gauge.
• During the installation, care should be taken not
to damage electric wires.
NOTICE
• Thoroughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to
the turbo fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduc-
tion, spraying, dispersing of water drops, drain pump malfunction, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient
capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it
may not suck in oily steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in
suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
10 Ceiling Cassette Air Conditioner
Air conditioner
Take enough
distance
Included Paper
787(TM/TN/TP)
840(TM/TN/TP)
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Cardboard on the bottom
of packaging
585~660(TQ)
875(TM/TN/TP)
517(TQ)
570(TQ)
Unit: mm
Ceiling
Level gauge
Ceiling board

Advertisement

Table of Contents
loading

Table of Contents