Download Print this page

Whitehall Best-Care Corterra WH3776 Installation, Operation And Maintenance Manual page 12

Ligature resistant corner basin ada compliant

Advertisement

Instructions for Operation and Care of Best-Care WH3776
VALVE INSTALLATION & ADJUSTMENT
Valve Assembly Installation:
NOTE: Installation should be in accordance with
accepted plumbing practices.
1) Locate suitable place for mounting the Valve
Assembly. Valve Assembly should be
accessible for service and adjustment and
as close to the point-of-use as possible.
Wall Anchors and Anchoring Hardware are
by others.
2) Connect hot and cold water to Supply
Valve using 1/2" NPTE connections.
3) Connect outlet of Tempering Valve to
Spout(s) using 1/4" O.D. Tube connections
provided.
4) Turn on hot and cold water supplies. If any
leaks are observed, hand-tighten
connections as necessary to stop leaks
before proceeding.
5) Turn on fixture and allow water to flow for 2
minutes. Measure water temperature at
outlet. If water is not at desired temperature,
adjust as necessary.
HINT: Angle Stops are recommended
and is the responsibility of the installer.
TEMPERATURE
STEM
WARMER
10
WHITEHALL MANUFACTURING • P .O. BOX 3527 • City of Industry, CA 91744-0527 U.S.A
Phone (800) 782-7706 • (626) 968-6681 • Fax (626) 855-4862 • Web: www.whitehallmfg.com
!
IMPORTANT
Flush supply lines of all foreign material such
as pipe dope, pipe chips, solder, sand etc.
before making up supply connections.
LOCKNUT
Temperature Adjustment:
NOTE: Factory set temperature is 105º F
1) Loosen Locknut.
2) Turn on fixture and run water for at least 2
minutes. Allow supply temperature to
stabilize.
3) Turn temperature stem counter-clockwise
for hotter or clockwise for colder outlet
temperature.
4) Tighten Locknut to prevent accidental or
unauthorized temperature adjustment.
5) Re-check outlet temperature.

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Best-care corterra wh3776lBest-care corterra wh3374l