Hide thumbs Also See for KNX T-AP:

Advertisement

Quick Links

Temperature Sensor
KNX T-AP
Installation and Adjustment

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KNX T-AP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for elsner elektronik KNX T-AP

  • Page 1 Temperature Sensor KNX T-AP Installation and Adjustment...
  • Page 2: Table Of Contents

    OR Logic 1 / 2 / 3 / 4 ..........................27 Linkage inputs of OR logic ........................28 KNX T-AP | from software version 0.2.0, ETS programme version 2.0 | Version: 29.03.2012. Errors excepted. Subject to technical changes. Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 •...
  • Page 4: Product Description

    The sensor can receive an external measured value via the bus and process it with the own data to an overall temperature (mixed value). The KNX T-AP provides four switching outputs with adjustable threshold values as well as additional AND and OR logic gates. The sensor has got a PI controller for heating and cooling.
  • Page 5: Installation And Commissioning

    Communication objects: Measurement range: -40…+80°C Resolution: 0.1°C Accuracy: ±1°C at -10…+85°C ±1.5°C at -25…+150°C The following standards have been considered for the evaluation of the product in terms of electro magnetic compatibility: Transient emissions: • EN 60730-1:2000 Section EMV (23, 26, H23, H26) (threshold category: B) •...
  • Page 6: Installation Position

    Elsner Elektronik does not assume any liability for changes in standards after publication of this instruction manual. Installation position The sensor is designed for surface mounting. When selecting an installation location, please ensure that the measurement results are affected as little as possible by external influences.
  • Page 7: Connection Of The Temperature Sensor

    Connection of the temperature sensor Remove the screwed on cover. Lead the KNX bus connection cable through the cable entry on the bottom of the casing and connect the bus +/- to the terminal provided for this purpose. Screw the cover back on. Notes on installation Do not open the temperature sensor if penetration of water (rain) is likely: Only a couple of drops could damage the electronic.
  • Page 8: Transmission Protocol

    Transmission protocol Abbreviations Flags: Communication Read Write Transmit Update Listing of all communication objects No. Name Function Flags External measured value for temperature Input 9.001 Internal measured value for temperature Output 9.001 C R T Total measured value for temperature Output 9.001 C R T...
  • Page 9 No. Name Function Flags Temp. threshold value 3: Absolute value Input / Output 9.001 C R W T U Temp. threshold value 3: (1:+ | 0:-) Input 1.006 Temp. threshold value 3: Output 1.001 C R T Switching output Temp. threshold value 3: Input 1.006 Switching output block...
  • Page 10 No. Name Function Flags Temp. control: Target value heating, Input / Output 9.001 C R W T U night Temp. control: TargetV heating, night Input 1.002 (1:+ | 0:-) Temp. control: Target value cooling, Input / Output 9.001 C R W T U night Temp.
  • Page 11 No. Name Function Flags AND logic 4: 1 bit Output 1.001 C R T AND logic 4: 8 bit output A Output 5.010 C R T AND logic 4: 8 bit output B Output 5.010 C R T OR logic 1: 1 bit Output 1.001 C R T...
  • Page 12: Setting Of Parameters

    Setting of parameters General settings Transmission delays after power-up and programming for: Measured values 5 s • 10 s • 30 s • 1 min • … • 2 h Threshold values and switching outputs 5 s • 10 s • 30 s • 1 min • … • 2 h Target values and actuating variables 5 s •...
  • Page 13: Temperature Measured Value

    Temperature measured value Temperature offset in 0.1°C -50 … 50 Use external measured value for temperature No • Yes If no external measured value is used: Use external measured value for temperature Temperature measured value • do not send • send periodically •...
  • Page 14: Temperature Threshold Values

    Internal and total measured value for • do not send temperature • send periodically • send in case of change • send in case of change and periodically All following settings refer to the total measured value From change of 2% •...
  • Page 15: Temperature Threshold Value 1 / 2 / 3 / 4

    Temperature threshold value 1 / 2 / 3 / 4 Temperature threshold value: …………………………… Temperature threshold value standard per Parameter • Communication object If the threshold value is set per Parameter: Temperature threshold value standard per Parameter Temperature threshold value in 0.1°C -300 …...
  • Page 16 The value communicated last shall be • not maintained • after restoration of voltage • after restoration of voltage and programming (Do not use for first commissioning) Start temperature threshold value in 0.1°C -300 … 800 valid until 1.communication (only if the value communicated last is “not” maintained or “after restoration of voltage”) Type of threshold change for temperature •...
  • Page 17 The behaviour with release of the switching output depends on the value of the parameter “Temperature switching output sends …” (see ”Temperature switching output”) Value of parameter Setting options “Behaviour of switching “Temperature switching output sends”: output with release”: on change •...
  • Page 18: Temperature Pi Control

    Temperature PI control Use control No • Yes If the control is in use: Control general: …………………………… Type of control • One-stage heating • Two-stage heating • One-stage cooling • One-stage heating + one-stage cooling • Two-stage heating + one-stage cooling •...
  • Page 19 Value of the blocking object 0 • 1 before 1. communication Send actuating variables • on change • on change and periodically Transmission cycle 5 s … 2 h (only if sending „periodically“) Status object/s send • on change • on change to 1 •...
  • Page 20 Heating control / Heating control 1. stage (Appears only if heating control is used): …………………………… Setting of the controller by • preset applications • controller parameter Application • Hot water heating (only if controller is set by “preset • Floor heating applications”) •...
  • Page 21 With release, the actuating variable follows the control Presetting for “preset applications”: Maximum actuating variable is Re-setting time reached at target/actual difference Hot water heating 5°C 150 min Floor heating 5°C 240 min Fan convector 4°C 90 min Electrical heating 4°C 100 min Heating control 2.
  • Page 22 Maximum actuating variable is reached at 1°C • 2°C • 3°C • 4°C • 5°C target/actual difference of (Attention: Can only be adjusted if “Setting of the controller by controller parameter”) Re-setting time in mins 1 … 255 (Attention: Can only be adjusted if “Setting of the controller by controller parameter”) If blocked, the actuating variable shall •...
  • Page 23 Night lowering …………………………… Use night lowering No • Yes If night lowering is used: Use night lowering Night lowering for object value • 1 = active | 0 = not active • 0 = active | 1 = not active Value of the activation object 0 •...
  • Page 24 The value communicated last shall be • not maintained • after restoration of voltage • after restoration of voltage and programming (Do not use for first commissioning) Start target value heating in 0.1°C -300 … 800 valid until 1.communication (if the heating control is used and only if the value communicated last is “not”...
  • Page 25: Logic

    Logic Communication objects logic inputs do nor release • release AND logic: …………………………… Logic 1 / 2 / 3 / 4 not active • active OR logic: …………………………… Logic 1 / 2 / 3 / 4 not active • active...
  • Page 26 AND Logic 1 / 2 / 3 / 4 1. / 2. / 3. / 4. Input • do not use • all switching events which the sensor provides (see “Linkage inputs of the AND logic”) Logic output sends not • one 1 bit object • two 8 bit objects If the logic output sends one 1 bit object: Logic output sends one 1 bit object...
  • Page 27: Linkage Inputs Of And Logic

    If logic = 1 object B value 0 … 255 If logic = 0 object B value 0 … 255 Communication objects • on change of logic AND Logic 1 A and B send • on change of logic to 1 •...
  • Page 28: Or Logic 1 / 2 / 3 / 4

    OR Logic 1 / 2 / 3 / 4 1. / 2. / 3. / 4. Input • do not use • all switching events which the sensor provides (see “Linkage inputs of the AND logic”) Logic output sends one 1 bit object • two 8 bit objects If the logic output sends one 1 bit object: Logic output sends ein 1 Bit-Objekt...
  • Page 29: Linkage Inputs Of Or Logic

    If logic = 1 object B value 0 … 255 If logic = 0 object B value 0 … 255 Communication objects • on change of logic OR Logic 1 / 2 A and B send • on change of logic to 1 •...
  • Page 30 Elsner Elektronik GmbH Steuerungs- und Automatisierungstechnik Herdweg 7 D-75391 Gechingen Germany Phone: +49 (0) 70 56/93 97-0 Fax: +49 (0) 70 56/93 97-20 info@elsner-elektronik.de http://www.elsner-elektronik.de...

Table of Contents