ADTRAN TOTAL ACCESS 4303 PLUS Job Aid

Dc power supply

Advertisement

Quick Links

DC SUPPLY
FRONT PANEL LEDs
G G
POWER
CLEI: SLPOCDBC_ _
G
G
G
PLUS
G G
TEMP
G
DESCRIPTION
The Total Access
the voltages necessary for proper system operation. The unit features LEDs for over-
temperature and DC output, an input fuse, and the ability to be hot-swapped when
used with another DC supply in the same chassis. The supply interfaces to the Total
Access backplane through a 48-pin connector. The unit accepts one or two –48 VDC
inputs from the backplane and supplies –48 VDC fused output for use with external
input logic, +5 VDC as hot insertion bias voltage for modules, and +2.1 VDC for back-
plane termination. In addition, the Total Access 4303 Plus DC Supply provides alarm
relay ouputs when installed in slot PS-A.
The following features are supported on the Total Access 4303 Plus DC Power Supply:
I
Thermal limit indicator with open collector output
I
DC status indicator on the 2.1 and 5 volt outputs with open collector output
I
Short circuit protection
I
Compatible with existing Total Access DC Power Supplies (P/N 1200335L1)
SPECIFICATIONS
Specifications
Input Voltage
Operating Temperature
Storage Temperature
Relative Humidity
Over Temperature Indication
–48 VDC Short Circuit Protection
Backplane Voltage Short Circuit Protection
Compliance
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
TOTAL ACCESS 4303 PLUS DC POWER SUPPLY
Off
Both –48 VDC fuses blown, power not supplied to the shelf,
or incorrect polarity on the voltage supplied to the shelf
Green
Power supplied is the correct voltage and polarity; backplane
and hot insertion voltages correct
Amber
–48 VDC input and hot insertion voltage present; no back-
plane voltage
Red
–48 VDC input present; no backplane voltage and no hot
insertion voltage
Off
Normal
Red
Over-temperature condition
®
4303 Plus DC Power Supply is a removable assembly that provides
–42 VDC to –56 VDC
–40°C to +65°C
–40°C to +85°C
Up to 95% noncondensing
90°C ±5%
Fused 1-amp slow blow
Self-mending
FCC Part 15, UL 60950, NEBS Level III,
GR-1089-CORE
ALARM RELAYS
There are eight alarm relays that provide normally open or normally closed
contacts for each of the following alarms:
I
Visual Critical
I
Visual Major
I
Visual Minor
I
Audible Critical
I
Audible Major
I
Audible Minor
I
Auxiliary 1
I
Auxiliary 2
POWER SUPPLY 48 PIN CONNECTOR PINOUT
Pin #
Row A Signal
Row B Signal
1
AUD_CRIT_NO
AUD_CRIT_COM
2
AUD_MAJ_NO
AUD_MAJ_COM
3
AUD_MIN_NO
AUD_MIN_COM
4
VIS_CRIT_NO
VIS_CRIT_COM
5
VIS_MAJ_NO
VIS_MAJ_COM
6
VIS_MIN_NO
VIS_MIN_COM
7
AUX1_RLY_NO
AUX1_RLY_COM
8
AUX2_RLY_NO
AUX2_RLY_COM
9
–48V_A
PS_OK
10
–48V_B
2.1V
11
2.1V
2.1V
12
–48V_AB_RTN
2.1V
13
GND
GND
14
GND
GND
15
GND
PSRLY_LOAD
16
FR_GND
–48V
JOB
A
ID
61202335L1-22A
0401
Row C Signal
AUD_CRIT_NC
AUD_MAJ_NC
AUD_MIN_NC
VIS_CRIT_NC
VIS_MAJ_NC
VIS_MIN_NC
AUX1_RLY_NC
AUX2_RLY_NC
PS_TEMP
PS_PRESENT
2.1V
VCC
GND
PSRLY_CLK
PSRLY_DATAIN
PSRLY_DATAOUT

Advertisement

loading

Summary of Contents for ADTRAN TOTAL ACCESS 4303 PLUS

  • Page 1 In addition, the Total Access 4303 Plus DC Supply provides alarm relay ouputs when installed in slot PS-A. The following features are supported on the Total Access 4303 Plus DC Power Supply: Thermal limit indicator with open collector output DC status indicator on the 2.1 and 5 volt outputs with open collector output...