3.3 Communication Port Explanation

The UPS is equipped with a true RS-232 communication port as standard to
provide communication with bundled UPS monitoring software for remote
monitoring of the UPS status using a PC.
In addition, there are six optional interface cards available to meet various
communication needs: USB, EPO/ROO, DCE (dry contact relay card), R2E, USE,
and an SNMP/Web card. (Please see Chapter 8.)
The software bundled with the UPS is compatible with many operating systems,
including Windows 98 / Me / NT / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 , Novell,
NetWare, Unix, Linux 2.6.x, Mac OS X v10.5 Leopard, Mac OS X v10.6 Snow
Leopard please contact your local dealer for suitable software.
All communication ports including optional cards can be active and used
simultaneously to monitor the UPS status. However, only one communication
interface at a time (the one with the highest priority) can control the UPS. The
priorities of these communication interfaces are as follows (highest priority first).
3.3.1 True RS-232
The RS-232 interface must be configured as follows.
Pin Assignments:
3.3.2 EPO/ROO
Pin Assignments:
1) EPO/ROO input port
2) Optional interface card
3) USB
4) RJ11/RJ45 Communication surge protection
5) RS-232
Baud Rate
Data Length
Stop Bit
Parity
Pin 3: RS-232 Rx
Pin 2: RS-232 Tx
Pin 5: Ground
2400 bps
8 bits
1
None
Function setting :
EPO NC  Shutdown UPS (default)
1.
EPO NO  Shutdown UPS
2.
ROO NC  Start-up UPS
3.
ROO NO  Start-up UPS
4.
(this function setting by setting tool )