LG BACnet Touch Installation & Owner's Manual page 37

Air conditioner
Table of Contents

Advertisement

Remarks
• Point NO. 1
1. The command executed is transmitted to the A/C regardless of the status of the A/C.
2. Present_Value property will not be used if a property has never been set in the past.
• Point NO. 2
1. If there is an operation error, the Present_Value property will be set to ACTIVE regardless of
whether the A/C is in operation or not.
• Point NO. 7
1. The Present_Value property will be set to "1: Cool" as the default value if property has never
been set in the past.
2. The air conditioner will ignore the command to an object that does not have right to select
operation mode. Therefore, the controlled/monitored system must not use this object for the air
conditioner without the right to select operation mode.
• Point NO. 11
1. The A/C will disregard the command which the object which can't select the operation mode.
Therefore, controlled/monitored system shouldn't use the object which can't select the operation
mode.
• Point NO. 12
1. Present_value property will be set to "1:Low" as the default result if the property has not been set
in the past.
• Point NO. 13
1. This unit is for indoor units only, and the approximate set temperature range is 18 ~ 35 °C.
2. When COV registration is made, the COV will be reported the moment a temperature change of
at least 0.5 °C is detected.
• Point NO. 14/ 19
1. This object is for indoor units only, and reports the room temperature data measured by the
indoor units.
• Point NO. 16
1. This object's error code descriptions should be referred to the corresponding table at the
"Reference LG original Error Code".
• Point NO. 35 ~ 49
1. This objects are effective, in case 2Set Auto Mode of environment setting is enabled.
FUNCTIONAL SPECIFICATIONS AC Smart BACnet
29