Advertisement

AC Smart BACnet's RS485 connection
An AC Smart BACnet can have up to 128 indoor units. If there are many outdoor units to be
connected, connect them to a bus. If not, AC Smart BACnet may malfunction.
<Good example: RS485 BUS form connection>
NOTES
Maximum node numbers which can be connected to RS485 communication line.
Multi V
y
Maximum of 16 nodes can be connected to 1 RS485 line.
Multi/Single
y
Maximum of 32 nodes can be connected to 1 RS485 line.
ERV
y
Maximum of 32 nodes can be connected to 1 RS485 line.
<Bad example: RS485 STAR form connection>