Emerson Fisher 67D Series Installation Manual

Emerson Fisher 67D Series Installation Manual

Hide thumbs Also See for Fisher 67D Series:

Advertisement

Quick Links

Installation Guide
D103151X014
English – April 2017
Introduction
This installation guide provides instructions for
installation, startup and adjustment. To receive a copy
of the instruction manual, contact your local Sales
Office or view a copy at www.fisher.com. For further
information refer to: 67D Series Instruction Manual,
form 5858, D103151X012.
P.E.D. Category
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using sound engineering
practice (SEP) per table below. For information on the
current PED revision see Bulletin: D103053X012.
PRODUCT SIZE
1/2 NPT
Specifications
Body Size and End Connection Style
1/2 NPT
Maximum Inlet Pressure (Body Rating)
Filtered models: 17.2 bar / 250 psig
Unfiltered models: 27.6 bar / 400 psig
Maximum Emergency Outlet Pressure
10.3 bar / 150 psig over outlet pressure setting up
to a maximum of 17.2 bar / 250 psig
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive.
Outlet Pressure Ranges
0 to 1.4 bar / 0 to 20 psig
0 to 2.4 bar / 0 to 35 psig
0 to 4.1 bar / 0 to 60 psig
0 to 8.6 bar / 0 to 125 psig
0 to 10.3 bar / 0 to 150 psig
Temperature Capabilities
With Nitrile (NBR)
Standard Bolting: -29 to 82°C / -20 to 180°F
Stainless Steel Bolting: -40 to 82°C / -40 to 180°F
With Fluorocarbon (FKM)
Polyethylene Filter
0 to 180°F
Polyvinylidene (PVDF), Stainless Steel or Glass
Filter (Optional): -18 to 149°C / 0 to 300°F
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
2. Do not use in high aromatic hydrocarbon service.
3. Silicone (VMQ) is not compatible with hydrocarbon gas.
CATEGORIES
FLUID TYPE
SEP
1
(1)
(1)
(1)
(1)
(standard): -18 to 82°C /
(2)
Temperature Capabilities
With Silicone (VMQ)
Temperature Nitrile (NBR) O-rings and Low
Temperature Bolting: -51 to 82°C / -60 to 180°F
With Gauges: -29 to 82°C / -20 to 180°F
With Automatic Drain: 4 to 79°C / 40 to 175°F
Installation
!
Only qualified personnel should install
or service a regulator. Regulators
should be installed, operated and
maintained in accordance with
international and applicable codes
and regulations and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If the regulator vents fluid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately
may create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping fluid or bursting
of pressure-containing parts may result
if this regulator is overpressured or
is installed where service conditions
could exceed the limits given in
the Specifications section or where
conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping
fluid. To avoid such injury and damage,
install the regulator in a safe location.
The internal relief valve in the
Types 67DFR and 67DFSR regulators do
not provide full overpressure protection.
The internal relief valve is designed for
minor seat leakage only.
67D Series
(continued)
(1)
Diaphragm, Low
(3)
WARNING

Advertisement

loading

Summary of Contents for Emerson Fisher 67D Series

  • Page 1 (SEP) per table below. For information on the maintained in accordance with current PED revision see Bulletin: D103053X012. international and applicable codes and regulations and Emerson Process PRODUCT SIZE CATEGORIES FLUID TYPE Management Regulator Technologies, 1/2 NPT Inc.
  • Page 2 67D Series Taking Out of Service (Shutdown) Clean out all pipelines before installation of the regulator and check to be sure the regulator has not been damaged or has collected foreign material during shipping. For NPT bodies, apply pipe compound to WARNING the external pipe threads.
  • Page 3 67D Series GE31805_B Figure 1. Types 67DFS and 67DFSR Assembly GE31806_A Figure 2. Types 67DS and 67DSR Assembly...
  • Page 4 Technologies, Inc. All rights reserved. 05/17. McKinney, Texas 75070 USA Singapore 128461, Singapore The Emerson logo is a trademark and service mark of Emerson T +1 800 558 5853 T +65 6770 8337 Electric Co. All other marks are the property of their prospective owners.

This manual is also suitable for:

Fisher 67dsFisher 67dsrFisher 67dfsFisher 67dfsr