DET3
Series
Final Heater Assembly
Chart 3.6
Tube Installation Sequence, Baffle Location and
Secured Joints for Reflectors
20 Foot
30 Foot
40 Foot
50 Foot
60 Foot
Burner Control Box with
16" Burner Tube
Primary Combustion
Chamber Tube
Secondary Aluminized Steel
Combustion Chamber
(150-200 MBH models only)
Stainless steel clamp location on 150 - 200 MBH models (P/N: TP-220).
Aluminized steel secondary combustion chamber location on 150-200 MBH models.
Stainless steel clamp location on 150 - 200 MBH models (P/N: TP-220).
Aluminized steel secondary combustion chamber location on 150-200 MBH models.
Stainless steel clamp location on 150-200 MBH models (P/N: TP-220).
Aluminized steel secondary combustion chamber location on 150-200 MBH models.
Key
27
3.0
Installation
•
Final Heater Assembly
NOTE: When securing joints on reflectors
which are rotated on an angle from horizontal,
secure joint only on top side of reflector to allow
for sufficient heater expansion and contraction.
1 to 45° Mounting Angle
0° Mounting Angle
Hot-rolled Steel Radiant
Emitter Tube
Standard Tube Clamp
Stainless Steel Tube
Clamp (P/N: TP-220)
150-200 MBH models only - Located
between 1st and 2nd 10 ft. tube sections.
Baffle Location