Venting - Brant Radiant Heaters DET3-20-65 User Manual

Gas-fired infrared tube heater det3 series
Hide thumbs Also See for DET3-20-65:
Table of Contents

Advertisement

3.0
Installation

Venting

Venting
The DET3 Series tube heater must be vented as described here to properly direct flue gases from the unit
to the outside atmosphere. The venting can terminate vertically through the roof (up) or horizontally
through a sidewall (sideways).
Follow these guidelines and all applicable codes for all models prior to installing the vent material. Local
codes may vary.
In the absence of local codes, refer to:
United States: NFPA 54/ANSI Z223.1 (latest edition), National Fuel Gas Code.
Canada: CAN/CGA B149.1 Installation Codes for Gas Burning Appliances.
release gas into the building which could result in health problems, carbon monoxide poisoning or death.
Improper venting may result in fire, explosion, injury or death.
Do not vent this appliance into another heater's vents or through a masonry chimney.
Do not use dampers in the heater vent pipe.
Single Wall vent pipe must not pass through any unoccupied attic, inside wall, concealed space, or floor.
Un-insulated single wall vent pipe must not be used outdoors for venting appliances in regions where
winter design temperature is below freezing.
Replacing Existing Equipment
If the heater is replacing existing equipment and using an existing vent system, inspect the venting for
proper size and horizontal pitch as directed in these instructions and the latest edition of the National Fuel
Gas Code, ANSI Z223.1 (NFPA 54) or CSA B149.1 Installation Code.
Determine that there is not blockage or restriction, leakage, corrosion or other deficiencies that can cause
hazards. The vent pipe should be corrosion-resistant galvanized steel of a thickness that meets the
National Fuel Gas Code. Minimum thickness for connectors varies depending on the pipe diameter. Never
vent the DET3 Series with PVC or plastic pipe.
If replacing an existing heater, vents may require re-sizing. Improperly sized venting
systems can result in vent gas leakage or condensation. Refer to the National Fuel Gas
Code ANSI Z223.1 (NFPA 54) or CSA B149.1 - latest edition. Failure to follow these
instructions can result in serious injury or death.
!
WARNING
Gas-fired heaters must be vented. A built in power exhauster is
provided. Additional external power exhausters are not required
or permitted.
Insufficient ventilation and/or improperly sealed vents may
!
WARNING
!
WARNING
28
DET3
Series