Digital_Input - Crestron SIMPL+ Reference Manual

Language reference guide
Hide thumbs Also See for SIMPL+:
Table of Contents

Advertisement

Crestron SIMPL+
Language Reference Guide - DOC. 5797G
®

DIGITAL_INPUT

Name:
DIGITAL_INPUT
Syntax:
DIGITAL_INPUT <var1>[,<var2>...];
DIGITAL_INPUT <var[size]>;
DIGITAL_INPUT <var[size[,min]]>;
Description:
Routes digital inputs from the outside SIMPL program into a SIMPL+ program under
the specified variable names. DIGITAL_INPUT values are either 0 (digital low) or 1
(digital high). Refer to the discussion on arrays on
NOTE: DIGITAL_INPUT variables may not be passed to functions in Version 3.00
for the 2-Series Control Systems. If you need to pass a DIGITAL_INPUT variable to
a function, assign it to a locally declared variable and pass that variable to the function.
NOTE: <min> is the number of inputs shown at a minimum in SIMPL Windows. The
Default is 1. The user can expand the minimum up to the full size. Only the last array
of a type can have <min>. Refer to Arrays on
For an array of DIGITAL_INPUTs, the maximum value of SIZE is 65535. Valid
indices are 1 through the specified size.
Example:
DIGITAL_INPUT osc_in, toggle_in;
Signifies that two digital inputs are coming into the SIMPL+ program from the
SIMPL Program.
DIGITAL_INPUT status_bits[8];
Signifies that up to eight digital inputs are coming into the SIMPL+ program from the
SIMPL Program, referenced under the names status_bits[1] through status_bits[8].
DIGITAL_INPUT flags[8,2];
Signifies up to eight digital inputs, with at least two shown.
Version:
SIMPL+ Version 3.01 for fixed arrays and minimum sizes.
SIMPL+ Version 2.00 for DIGITAL_INPUT arrays.
SIMPL+ Version 1.00 for everything else.
Software
page
46.
page
31, and Declarations on
SIMPL+
page
45.
®
51