PREPARING THE CABINET - FLAT TOP BOTTLE COOLERS

Refrigerant

All models covered in this user manual are
manufactured using refrigerant R290 (Propane).
R290 is a hydrocarbon. This refrigerant is
flammable and is only allowed for use in
appliances which fulfill the requirements of UL
471 (To cover potential risk originated from the
use of flammable refrigerants). Consequently,
R290 is only allowed to be used in refrigerating
appliances which are designed for this
refrigerant and fulfill the above-mentioned
standard.
R290 is heavier than air. The concentration
will always be highest at floor level.
The explosion limits are as follows:
- Lower Limit: 1.7% by vol. (37 g/m3)
- Upper Limit: 9.5% by vol. (177 g/m3)
- Ignition Temperature: 470 °C
Take caution when handling,
DANGER
moving and using the product
to avoid damaging the refrigerant tubing or
increasing the risk of a leak.
All service work shall
WARNING
be performed by factory
authorized service personnel and all
component parts shall be replaced with like
components to minimize the risk of possible
ignition due to incorrect parts or improper
service.
If service is necessary,
CAUTION
repair work must be performed by a
Perlick authorized servicer. Work done by
unqualified individuals could potentially be
dangerous and will void the warranty.

Uncrating and Inspection

Remove all crating material. Carefully inspect
cabinet for hidden damage. If damage is
discovered, file your claim immediately with the
transport company. Perlick is not responsible for
damage in transit.
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
Printed in USA
Flat Top Bottle Coolers Installation & Operation Manual

Plumbing

No plumbing connections are required.
Condensate from the cooling coil automatically
evaporated through a condensate pan located in
the condensing unit section.

Electrical

The cabinet must be connected to a separately
fused power source (see Electrical Specification
Plate affixed to unit) in accordance with National
and Local electrical codes.
Do not operate the equipment
DANGER
without a light bulb installed. Socket is live
when equipment power is on.
Do not attempt to operate the
CAUTION
equipment on any other power source than
that listed on the Electrical Specification Plate.
Adjustable Partitions & Shelving
Perlick Bottle Coolers may be provided with
adjustable partitions and shelving which will
accommodate various bottle sizes.
■ Remove bottles and cans from their cases
before placing in cooler to ensure proper
air flow.
■ When loading product into cabinet, care must
be taken to avoid blocking airflow into and out
of the evaporator. Maintain at least 2" of
clearance on evaporator air intake and
exhaust for proper operation.
Installing Casters or Legs (optional)
Attach casters or legs to the cabinet bottom in
holes provided. Use the supplied 1/4" - 20 hex
head self-tapping machine screws. If unit is tipped
on its back for an extended period of time, wait
24 hours after unit is uprighted to plug the unit in.

Placing the Cabinet

To assure maximum performance, fresh air must
be allowed to circulate through the machinery
compartment. It is important to allow at least
two inched of clearance at the back or left end
of the cabinet. Do not place anything in front of
the cabinet that would obstruct air flow at these
grilles. Do not place the unit in an unventilated
small room.