N.B.
It is not allowed to write a CBE for a direct group, if the operands contained inside the round brackets
are some groups having an index lower than the group for which the CBE must be associated as in the
following example:
CBE not allowed
CBE allowed
It is not allowed to write a CBE for an inverse group, if the operands contained inside the round
brackets are some groups having an index higher than the group for which the CBE must be associated
as in the following example:
CBE not allowed
CBE allowed
is the operator which requires AT LEAST TWO elements of the group indicated below, to be ACTIVE.
FORMAT : XGRP (GXXX)
Example: the equation of an output module is XGRP (G23)
- IF ANY COMBINATION of two or several input devices (sensors or modules), which have been programmed
(with their CBE Equation) on this software group (through the Double Consent parameter = YES.), they are
ACTIVE.
THEN this output module will be activated.
-
Or only when a thermal sensor
(through their CBE Equation) on this software group (through the Double Consent parameter = NO), are ACTIVE.
-
THEN this output module will be activated,
-
It is not allowed to write an equation of an output module with several groups as in the following
example:
CBE not allowed
Pag. 50
NOTIFIER ITALIA
G33 = (G23 G24)
G21 = (G23 G24)
G305 = (G306 G307)
G307 = (G305 G306)
XGRP
where GXXX= Group 1  400
( type-id "THER") and an optical sensor (type-id "PHOT" ) which have been programmed
XGRP (G23 G24)