Minimum Clearance To Combustibles; Introduction; Location; Air For Combustion And Ventilation - Bryant 362AAN Installation, Start-Up, And Operating Instructions Manual

Low-boy oil-fired furnace series b
Hide thumbs Also See for 362AAN:
Table of Contents

Advertisement

Only the latest issues of above codes should be used, and are
available from either The National Fire Protection Agency, Bat-
terymarch Park, Quincy, MA 02269 or The Canadian Standards
Association, 178 Rexdale Blvd., Rexdale, Ontario M9W 1R3
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
TABLE 1—MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS (IN.)
UNIT APPLICATION
Furnace
Sides
Supply Plenum and Warm-Air Duct Within 6 ft
of Furnace
Back
Furnace Casing or Plenum
Top
Horizontal Warm-Air Duct Within 6 ft of
Furnace
Bottom
Horizontally or Below Pipe
Flue
Pipe
Vertically Above Pipe
Front
* Floor may be combustible.
NOTE: Adequate service clearance should be provided over and above these
dimensions as required.

INTRODUCTION

The model 362AAN Furnaces are available in sizes 105,000
through 155,000 Btuh input capacities.
The furnace is shipped as a packaged unit, complete with burner
and controls. It requires a line voltage (115 vac) connection to
control box, a thermostat hook-up as shown on wiring diagram, oil
line connection(s), adequate duct work, and connection to a
properly sized vent.
The air handling capacity of this furnace is designed for cooling
airflow. Refer to Table 5 for expected airflows at various external
duct static pressures.

LOCATION

WARNING: This furnace is not water tight and is not
designed for outdoor installation. This furnace shall be
installed in such a manner as to protect electrical com-
ponents from water. Outdoor installation would lead to a
hazardous electrical condition and to premature furnace
failure.
WARNING: Do not use this furnace as a construction
heater. Use of this furnace as a construction heater
exposes furnace to abnormal conditions, contaminated
combustion air, and lack of air filters. Failure to follow
this warning can lead to premature furnace failure and/or
vent failure which could result in a fire hazard and/or
bodily harm.
This furnace is approved for reduced clearances to combustible
construction, therefore, it may be installed in a closet or similar
enclosure. It may be located in a basement or on the same level as
area to be heated. In any case, unit should always be installed level.
In a basement or when installed on the floor, it is recommended
that unit be installed on a concrete pad that is 1- to 2-in. thick.
On dirt floors, furnace may be installed on concrete blocks. Place
blocks under all 4 corners and under center of furnace. Center
block 22 in. from back of furnace forward.
.
The required minimum clearances for this furnace are specified in
Table 1.
The furnace should be located as close as possible to chimney or
vent in order to keep vent connections short and direct. The
furnace should also be located as near as possible to center of air
distribution system.
I. AIR FOR COMBUSTION AND VENTILATION
LOW-BOY
0
1
0
2
2
0*
This furnace should be installed in a location in which facilities for
4
ventilation permit satisfactory combustion of oil, proper venting,
8
and maintenance of ambient temperature at safe limits under
8
normal conditions of use. The location should not interfere with
proper circulation of air within the confined space. (See NFPA-31,
Section 1.5.)
In addition to air needed for combustion, process air shall be
provided as required for: cooling of equipment or material,
controlling dew point, heating, drying, oxidation or dilution, safety
exhaust, and odor control.
In addition to air needed for combustion, air shall be supplied for
ventilation, including all air required for comfort and proper
working conditions for personnel.
The barometric draft regulator (included with furnace) shall be
installed in same room or enclosure as furnace in such a manner as
to prevent any difference in pressure between regulator and
combustion-air supply.
Air requirements for operation of exhaust fans, kitchen ventilation
systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion-air
requirements.
In unconfined spaces in buildings of conventional frame, brick, or
stone construction, infiltration MAY be adequate to provide air for
combustion, ventilation, and dilution of flue gases. This determi-
nation must be made on an individual installation basis and must
take into consideration the overall volume of unconfined space, the
number of windows and ventilation openings, the number of doors
to the outside, internal doors which can close off unconfined space,
and overall tightness of building construction. Consideration must
also be given to the amount of storage items (furniture, boxes, etc.)
within the unconfined space which take away from the air volume.
Many new buildings and homes (and older ones that have been
weatherized) MUST BE considered as being of tight construction,
therefore, infiltration will not be sufficient to supply necessary air
for combustion and ventilation.
A building can be considered as being of tight construction when:
1. Walls and ceilings exposed to outside atmosphere have a
2. Weatherstripping has been added on operable windows and
—2—
WARNING: Installation of this furnace in an area where
it will receive contaminated combustion air must be
avoided. Such contamination would include the follow-
ing: ammonia, chlorine, hydrogen sulfide, halogenated
hydrocarbons, carbon tetrachloride, cleaning solvents,
hydrochloric acid, water softening chemicals, and similar
chemicals. Failure to follow this warning will lead to
premature rusting of heat exchanger and possible prema-
ture furnace failure and/or vent failure which could result
in fire hazard and/or bodily harm.
continuous water vapor retarder with a rating of 1 perm or
less with openings gasketed or sealed, and/or
doors, and/or

Advertisement

Table of Contents
loading

Table of Contents