C-LOGIC 625-MD Instruction Manual page 2

Ceiling mounting slimline presence detector

Advertisement

Available languages

Available languages

INSTRUCTIONS MANUAL
Ceiling mounting slimline presence detector
C-LOGIC 625-MD
SKU: CLOGIC625MD230VCBINT
ENGLISH
The product adopts good sensitivity detector and integrated circuit. It gathers automatism,
convenience, safety, saving-energy and practicality functions. The wide detection field con-
sists of up and down, left and right service field. It works by receiving human motion infrared
rays. When one enters the detection field, it can start the load at once and identify automati-
cally day and night. Its installation is very convenient and its using is very wide.
SPECIFICATION:
• Power Source: 220-240V~
• Detection Range: 360°
• Power Frequency: 50/60Hz
• Detection Distance: 10 m diameter (3 m height)
• Ambient Light: <3-2000LUX (adjustable)
• Working Temperature: -20~+40ºC
• Time Delay:
• Min.10sec±3sec
• Max.15min±2min
• Working Humidity: <93%RH
• Power Consumption: approx. 0.5W
• Rated Load:
• Max.2000W (incandescent lamp)
• 1000W (energy-saving and LED lamps)
• Detection Moving Speed: 0.6 - 1.5 m/s
• Installation Height: 2.2 - 4 m
• Protection degree: IP 20
FUNCTION:
• Can identify day and night: The consumer can adjust working state in different ambient
light. It can work in the daytime and at night when LUX knob is adjusted on the "sun"
position (max). It can work in the ambient light less than 3LUX when it is adjusted on the
"3" position (min). As for the adjustment pattern, please refer to the testing pattern.
• Time-Delay is added continually: When it receives the second induction signals within the
first induction period, it will compute time once more on the basic of the first time-delay rest.
INSTALLATION ADVICE:
As the detector responds to changes in temperature, avoid the following situations:
• Avoid pointing the detector towards objects with highly reflective surfaces, such as
mirrors etc.
• Avoid mounting the detector near heat sources, such as heating vents, air conditioning
units, light etc.
• Avoid pointing the detector towards objects that may move in the wind, such as curtains,
tall plants etc.
CONNECTION:
¡Warning! ¡Danger of death through electric shock!
• Must be installed by professional electrician.
• Disconnect power source.
• Cover or shied any adjacent live components.
• Ensure device cannot be switched on.
• Check power supply is disconnected.
• Please move the upper cover with anti-clockwise whirl as per the "Figure 1".
• Connect the power and the load according to the connection-wire diagram.
• Fix the bottom on the selected position with the inflated screw.
• Install back the upper cover on the sensor, then you could switch on the power and test it.
TEST:
• Turn the TIME knob anti-clockwise on the minimum (10s).Turn the LUX knob clockwise
on the maximum (sun).
• Switch on the power; the load and the indicator lamp don't work. After Warm-up 30sec,
the indicator lamp turns on .Under the condition of no sense signal, the load should stop
working within 10sec±3sec and the indicator lamp would turn off.
• After the first induction is out, make it sense again after 5~10sec. The load should work
again. when no sense signal, the load should stop working within10sec±3sec.
• Turn LUX knob anti-clockwise on the minimum (3). If the ambient light is more than 3LUX,
the sensor would not work and the lamp stop working too. If the ambient light is less than
3LUX (darkness), the sensor would work. Under no induction signal condition, the sensor
should stop working within 10sec±3sec.
Note: when testing in daylight, please turn LUX knob to
the sensor lamp could not work!
If the lamp is more than 60W, the distance between lamp and sensor should be 60cm
at least.
SOME PROBLEM AND SOLVED WAY:
• The load do not work:
a. Please check if the connection-wiring of power and load is correct.
b. Please check if the load is good.
c. Please check if the working light sets correspond to ambient light.
• The sensitivity is poor:
a. Please check if there has any hindrance in front of the detection window to affect to re-
ceive the signal.
b. Please check if the ambient temperature is too high.
c. Please check if the induction signal source is in the detection fields.
d. Please check if the installation height corresponds to the height showed in the instruction.
e. Please check if the moving orientation is correct.
• The sensor can not shut off the load automatically:
a. Please check if there is continual signal in the detection field.
b. Please check if the time delay is the longest.
c. Please check if the power corresponds to the instruction.
COVERAGE AREA
EN
SENSITIVITY
CONDITIONS TO AVOID
MOUNTING
Figura/Figure 1
TEST
MANUFACTURER: MGL International
APAC: MGL GLOBAL SOLUTIONS LTD
info.apac@mgl-intl.com
Flat 4-1, 4/F, No. 35, Section 3 Minquan
East Road. Taipei, Taiwan.
Tel: +886 2-2508-0877
(SUN) position, otherwise
EMEA: MGL EUMAN S.L.
info.emea@mgl-intl.com
Parque Empresarial Argame, 33163
Morcín. Asturias, Spain.
Tel: +34 985-08-18-70
h
Ø
Good sensitivity
CONNECTION-WIRE DIAGRAM
FULL MANUAL DOWNLOAD
You can download the complete manual at the
URL
https://clogic-intl.com/clogic-625-md
AMERICAS: MGL AMERICA, LLC.
info.na@mgl-intl.com
US East Coast: 2810 Coliseum Centre
Drive, Ste. 100. Charlotte, North Carolina,
28217 USA
Tel: +1 833 533-5899
US West Coast: 760 Challenger Street.
Brea, California 92821 USA
Tel: +1 310-728-6220
www.mgl-intl.com
Poor sensitivity

Advertisement

loading

This manual is also suitable for:

Clogic625md230vcbint