Fire Sentry FS7-130-SX and FS-130-SX2 Controllers
Installation Guide and Operating Manual
MAN0933_V1_1521-001_Rev E_08-12
1.3.8

FireBusII

All FS7-2173 Detectors are interconnected by the FireBusII. A maximum of 12
Detectors may be attached to any SX Controller and the maximum cable length is
1000 feet. The four-conductor FireBusII supplies the 12 VDC power and RS-485
digital communications to all Detectors. The Controller supervises the FireBusII line.
Improper FireBusII operation is indicated by the Controller Fault LED.
WARNING:
Figure 1: Model JB-4 Junction Box Enclosure Dimensions
Figure 2: FS7-130-SX / -SX2 Controller Enclosure Dimensions
(6 each) 0.154 +.005/-.002 DIA THRU
Connector J1: Ten pin removable terminal strip.
Connector J2: Ten pin removable terminal strip.
RS-232 Port:
Type DB-9 pin female serial communications bus.
The Controller requires 24 VDC. Under NO circumstances
should 120 or 240 VAC be applied to the Controller's input
power terminals or any other Controller connection
terminals.