Connecting Sensor Cable - YOKOGAWA DOX10 User Manual

Table of Contents

Advertisement

2.2.1

Connecting Sensor Cable

IM 12J05S01-01E
(1) Loosen two screws which are at front of power supply unit and detach the cover.
(2) Pull the cable into the power supply unit from sensor cable inlet hole.
(3) Connect the sensor cable to the terminals.
After passing the cable through the nut, check the color on each core wire, then
connect each core wire to the corresponding terminal.
DO70G Wiring Diagram Example
DO402G
Detail-1
DO70G
Connections of the sensor cable and DO402G terminals
are shown in the following table.
(Wiring color)
DO70G
Red
Clear
Green/Yellow
Green
White
Figure 2.4 Connecting Sensor Cable
(4) Mount the cable gland in the cable inlet hole.
Put the nut in place, and screw it onto the main body sufficiently. At this time,
loosen the packing gland so that the cable is not twisted. After fixing the main body,
tighten the packing gland to keep moisture out of the equipment. However if the
packing gland is screwed up too tight, the cable will be damaged.
DOX10
Detail-1(DO402G)
DO402G (Terminal No.)
18
17
14
12
11
2. Installation and Wiring
Detail-2
Detail-2(DOX10)
Connections of the sensor cable and DOX10 terminals
are shown in the following table.
(Wiring color)
DO70G
DOX10 (Terminal No.)
BROWN
+ BROWN
BLUE
- BLUE
K9679AX
2-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dox10-u-00-nDox10-u-15-n