OUTPUT
VOLTAGE
REQUIRED
MOTORS (Vdc)b
1
1.7
2
2.0
2.3 2.7
5
3.0
6
3.3
required to drive the motors.
SERIES 90 MOTORS OPERATION CHECK WITH MODUTROL MOTOR DISCONNECTED FROM CONTROLLER
STEP
ACTION
1.
Apply 24 Vaca.
Open terminal B and short W to R.
2.
3.
Open terminal W and short B to R.
4.
Connect terminals R to B to W.
5.
Remove jumpers from R, B, and W.
Check voltage between B and R,
and W and R.
6.
Motor does not drive.
Voltage out of range.
7.
8.
Disconnect 24 Vat.
NOTES:
input is in phase with all motors.

DAMPER APPLICATION

1. Turn off power and remove wiring from the old
actuator.
2. Remove crank arm from shaft of old actuator and
remove the old actuator.
whether or
3. Checkto see
needed. lf the linkage can reach the lowershaft position of
the new actuator and if the crank arm has clearance for the
needed rotation, then the bracket is not needed. Use
220738A Adapter Bracket or 221455A crank arm if crank
arm must rotate through the bottom plane of the motor (for
damper applications).
directly to the equipment and refer to the INSTALLATION,
SETTlNGS&ADJUSTMENTS,andCHECKOUTsections
of these instructions as needed.
Honeywell
U.S.A.: 1885 Douglas Drive N.
Golden Valley, MN 55422-4386
CANADA: 740 Ellesmere Road
Scarborough, Ontario Ml P 2V9
4-20 mA
RESISTOR (A)
(Ohms)
Part No.
237
150
802139BFAA
124 113
97.6"
position.
to their normal mechanical
position.
not the mounting bracket is
Inc.
International Sates Offices in all principal cities of the world. Manufacturing in
Australia, Canada, Finland, Franc%, Germany, Japan, Mexico, Netherlands,
Spain, Taiwan, United Kingdom, U.S.A.

CHECKOUT

After installation and linkage adjustment, check the entire
motor and control hookup to ensure that-
*
The motor operates the damper or valve properly.
The motor responds properly to the controller.
l
Inspect the motor, linkage, and valve or damper to see
that all mechanical connections are correct and secure. In
damper installations, the pushrod should not extend more
than a few inches past the ball joints. Check to see that
there is adequate clearance for the linkage to move
through its stroke without binding or striking other objects.
Check to see that cams operate the auxiliary switches,
if used, at the desired point of motor rotation.
NOTE: Motors are shipped in the fully closed position (the
limit of counterclockwise rotation as viewed from the
power end of the motor) with the stroke set at 90".
RESPONSE
None.
Motor drives closed.
Motor drives open.
Motor must drive to Mid-
17 to 20 Vdc.
Motor is defective.
Motor printed wiring board
is defective.
Spring return motors return
sections and see Fig. 3 as well as the INSTALLATION,
SETTINGS &ADJUSTMENTS, and CHECKOUTsections
of these instructions.
5. Use old mounting bolts to mount the new actuator.
6.
Mountthedampercrankarmandlinkagetotheshaft
of the new actuator.
8. Use the CHECKOUT procedures to test the proper
adjustment of the crank arm and linkage.

VALVE APPLICATION

When installing a M9484, M9494 motor in a valve ap-
plication which has a QlOO, Q601 or 0618 it will be
necessary to use the 220738A Adapter Bracket provided
to raisethe motorshafttothesame height asthatof theold
motor. Ensure motor stroke is 160" to operate Honeywell
IF NO OR LIMITED RESPONSE
Proceed to Step 6.
Proceed to Step 6.
Proceed to Step 6.
No voltage or out of range. Proceed
to Step 7.
Replace motor.
Replace motor.
Spring mechanism defective
-replace motor.
PRINTED IN U.S.A.