OPERATION AND CHECKOUT

Operation
In an operational circuit, a single-pole, single-throw controller
or fan starter (line voltage for Series 41, or low voltage for
Series 81) is wired in series with the motor circuit. When the
controller switch closes, the motor is energized and runs to
the end of its stroke. At this point, the internal motor limit
switch opens, de-energizing the motor. The brake solenoid is
energized, however, and remains so as long as the controller
is closed. The brake holds the motor in the energized position
until the controller opens. At this point, the brake is released
and the spring returns it to the starting position.
Checkout
After the installation is complete, check the entire system for
the following points of operation:
• Motor operates the load properly.
• Motor responds properly to the controller.
• Motor returns to starting position when power is interrupted.
63-2187—3
MOVE SCREWDRIVER AT
TOP ONLY TO ADJUST CAM.
RIGHT/INNER
AUXILIARY
SWITCH
INNER
AUXILIARY
CAM
(BLUE)
FAST RISE
PORTION
(APPROX.
1 DIFF.)
SLOW RISE
PORTION
(APPROX.
OUTER
10 DIFF.)
AUXILIARY
CAM
(RED)
MOTOR
MOTOR
CLOSE
OPEN
POWER
END
Fig. 13. Auxiliary switch adjustments.
NOTE: CAMS ARE OFFSET
VERTICALLY TO PROVIDE
BETTER VIEW OF BACK CAM.
LEFT/OUTER
AUXILIARY
POWER END
SWITCH
OF MOTOR
Damper Application
1. Check the entire motor-damper linkage to ensure that
the mechanical connections are secure and properly
made. Be certain the ball joint on the damper crank arm
is properly placed to give the required amount of travel.
2. Energize the motor and run it to the end of its stroke.
Check the damper linkage while the motor is running to
see that there are no loose or binding connections.
3. If the motor does not run, check the control circuit for an
open or short, the presence of power, and voltage at the
motor. Voltage at the motor must be at least 85 percent
of the rated voltage (specified on nameplate.) Ensure
that the maximum motor net load is not exceeded.
4. Interrupt the power to de-energize the motor and allow
the spring to return the motor to the starting position. If
the motor does not return, check to ensure that power is
actually interrupted and that the return load is not
exceeding the rated motor load.