Compressor Plug - Bryant R-22 Application Manual And Service Manual

Air conditioners and heat pumps using r-22 refrigerant
Table of Contents

Advertisement

THERMOSTAT
SUBBASE
L
L
THERMOSTAT
INDOOR
SUBBASE
UNIT
TERMINAL
BOARD
heat-pump output drops. Setting at which thermostat closes is
variable, depending on design of system. It is set at time of
installation and should not be changed without cause. Up to 2
outdoor thermostats may be installed. Some systems may not have
any thermostat. An outdoor thermostat can also be used to lock out
compressor operation at low ambients in condensing unit not
equipped with low-ambient control.
Although these devices are installed in control circuit (24v), turn
off all power to unit before attempting to troubleshoot thermostat.
Use a standard ohmmeter to check for continuity through thermo-
stat. If you suspect thermostat is out of calibration, use calibrated
electronic thermometer to determine correct outdoor temperature.
Turn thermostat dial knob until switch closes. Observe this using
ohmmeter across switch. Read temperature setting when switch
closes. It should be close to reading observed using electronic
thermometer. Any setting within ± 5°F is acceptable.
24-VOLT WIRING
C
Y
L
L
L
C
INDOOR
OUTDOOR
UNIT
UNIT
TERMINAL
TERMINAL
BOARD
BOARD
PASS SUPPLY WIRE THROUGH
METALLIC LOOP TWICE ON
UNITS WITH NAMEPLATE
RLA OF 14 AMPS OR LESS.
Fig. 25—Service Alarm Wiring Connections
FIELD LINE VOLTAGE SUPPLY WIRE
CYCLE PROTECTOR
YEL
T1
T2
T3
VIO
BLK
Y
L
C
BLK
C
BLK
C
BRN
OUTDOOR
UNIT
TERMINAL
BOARD
Fig. 26—Wiring Connections for Service Alarm and Cycle Protector
HIGH AND/OR LOW PRESSURE
AND/OR DISCHARGE TEMPERATURE
SWITCH (IF USED)
HPS
BRN
C
BLU
BLU
BLK
ORN
1
SERVICE ALARM
*METALLIC
LOOP
SERVICE ALARM
X
3
2
1
ORN
YEL
COMMON POTENTIAL
FACTORY WIRING (FIELD CONNECTED)
FIELD-SUPPLIED WIRING
C
CONTACTOR
XIII. COMPRESSOR PLUG
The compressor electrical plug provides a quick-tight connection
to the compressor terminals. The plug completely covers the
compressor terminals, and the mating female terminals are com-
pletely encapsulated in the plug. Therefore, the terminals are
isolated from any moisture so corrosion and resultant pitted or
discolored terminals are reduced. The plug is oriented to the relief
slot in the terminal box so the cover cannot be secured if wires are
not positioned in slot, assuring correct electrical connection at the
compressor. The plug can be removed by simultaneously pulling
while rocking the plug. However, these plugs are specialized and
vary in terminal orientation in the plug. Therefore, plugs can be
used on only the specific compressor or group as shown in Fig. 27.
For the Carlyle and Bristol compressors in Fig. 27, the triangle
formed by the fusite terminals points down, and the plug is
likewise oriented. The fusite terminals and plug-terminal orienta-
—24—
DTS
LPS
YEL
YEL
YEL
RED
2
3
X
ONE FIELD
LINE VOLTAGE
SUPPLY WIRE
HIGH AND/OR LOW PRESSURE
AND/OR DISCHARGE TEMPERATURE
SWITCH (IF USED)
DTS
YEL
BLU
LPS
HPS
A88340
C
BLU
BRN
A88339
A88339