Troubleshooting - Bryant PERFECT AIR 1620 Installation Instructions Manual

Air purifier for fan coils
Table of Contents

Advertisement

TROUBLESHOOTING

CAUTION
!
SAFETY HAZARD
Failure to follow this caution may result in personal injury
or equipment damage.
The following instructions are for use by qualified
personnel only.
WARNING
!
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning could result in personal injury
or death.
The following procedures will expose electrical components.
Disconnect power between checks and proceed carefully.
The Perfect Airt Air Purifier is equipped with a power indicator
light located on the door (see Fig. 13). This power indicator light
will illuminate when the Perfect Airt Air Purifier door is
installed, the power switch is in the on position, AND the fan coil
blower is running and airflow is sensed. If the power indicator
light is not illuminated, follow the troubleshooting steps below.
Step 1 —Check that the Perfect Airt Air Purifier door is
installed.
NOTE: A magnet in the door (see Fig. 8) is used to activate a
safety switch in the power supply when the door is installed. The
power supply will not energize the air purifier unless the safety
switch is activated.
Step 2 —Check that the Perfect Airt Air Purifier power switch
is in the on (closed) position.
Step 3 —Confirm that the fan coil blower is operating.
AND
HIGH
VOLTAGE
Step 4 —Confirm that 208/230 VAC power is provided. Attach
power supply connector to the air purifier when the fan coil
blower is operating.
NOTE: Even though power is supplied to the Perfect Airt Air
Purifier, it will not turn on unless the airflow sensor senses
airflow or the airflow sensor's bypass plug is inserted.
Step 5 —Confirm that the airflow sensor cable or airflow sensor
bypass plug is connected to the power supply (See Fig. 7).
Step 6 —If still not functioning, disconnect the airflow sensor
cable and the power cord from the power supply.
Remove the enhancement module from the air purifier cabinet
and inspect the airflow sensor (See Fig. 11).
Confirm the airflow sensor is properly seated in its bracket and
the airflow sensor cable is connected to the back of the sensor.
Replace the enhancement module.
Step 7 —Reconnect the power cord to the power supply and
insert the airflow sensor disable jumper (from parts bag).
If the power indicator light illuminates, then replace the airflow
sensor.
Install the door onto the air purifier and turn the power switch to
the "ON" position.
Step 8 —If all of the above steps are completed and the power
indicator light is still not illuminating, replace the power supply
on the enhancement module. Note that there are no serviceable
parts within the power supply.