10

Auto restart setting

This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function in
the on position.
How to cancel the Auto Restart
Auto restart (wired remote controller)
(When performing this task, be sure to use a wired
remote controller)
<Procedure> Perform setting while the air conditioner
stops.
1
Push
+
+
buttons simultaneously
for 4 seconds or more.
The rst displayed unit No. is the master indoor
t
unit address in the group control.
In this time, fan and louver of the selected indoor
unit operate.
2
Every pushing
button (button at
left side), the indoor unit No. in the group
control is displayed one after the other. In
this time, fan and louver of the selected
indoor unit only operate.
3
Using the set temperature
buttons,
specify the CODE No. (DN).
4
Using the timer time
TIME
buttons, select
the set data.
5
Push
button. (OK if indication lights)
To change the selected indoor unit, proceed to
2
Procedure
.
To change item to be set up, proceed to
3
Procedure
.
6
Pushing
button returns the status to the
normal stop status.
39-EN
TEMP.
ON / OFF
3
TIMER SET
FAN
MODE
6
TIME
SAVE
VENT
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
Setting
1
DN
Item
Description
Automatic
0000:
0001:
restart
None
Restart
28
of power
failure
11

Test run

Before test run
Before turning on the power supply, carry out the
following procedure.
By using 500V-megger, check that resistance
of 1 M
or more exists between the terminal
block 1 to 3 and the earth (grounding).
4
If resistance of less than 1 M
5
not run the unit.
Check the valve of the outdoor unit being
opened fully.
2
Execute a test run
At
shipment
Operate the unit with the wired remote controller as
0001:Restart
usual.
For the procedure of the operation, refer to the
attached Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
– 20 –
Wired remote controller
1,5
is detected, do
1
Push
button for 4 seconds or more.
[TEST] is displayed on the display part and
the selection of mode in the test mode is
permitted.
2
Push
button.
3
Select the operation mode with
button, [
C
o
o
. ] l
Do not run the air conditioner in a mode other
than [
Cool].
The temperature controlling function does not
work during test run.
The detection of error is performed as usual.
4
After the test run, push
stop a test run.
(Display part is same as procedure
5
Push
button to cancel (release from) the
test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
2, 4
3
button to
1
.)
EN
FR
40-EN