Multi Variable Air Conditioners One-way Cassette Type Indoor Unit
(3) Use pipe bend when bending the pipe and the bending angle should not be too small.
(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape.

4.3 Drainage Pipe Installation and Drainage System Testing

4.3.1 Notice for Installation of Drain Pipe
(1) The drainage pipe should be short and the gradient downwards should be at least 1%~2% in
order to drain condensation water smoothly.
(2) The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe
joint.
(3) Install drainage pipe according to the following fig and arrange insulation to the drainage pipe.
Improper installation may lead to water leakage and damp the furniture and other things in the
room.
(4) You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert the
end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire binder.
Can't connect the drainage hole and drainage hole with glue.
(5) When the drainage pipelines are used for several units, the position of pipeline should be
about 100mm lower than the drainage port of each unit. In this case, thicker pipes should be
applied.
additional drainage pipe
4.3.2 Drainage pipe installation
(1) Drainage pipe should have the same diameter or larger diameter than the connecting pipes
(PVC pipe, outside diameter 25mm, thickness≥1.5mm)
(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for preventing
forming air bubbles.
(3) If the gradient of drainage pipe could not meet the installation requirements, rasing pipe
should be applied.
(4) Insert the drainage hose into drain socket, tighten the metal clamp securely.
(5) Warp the sealing pad over drain hose and metal clamp for heat insulation.
(6) Make sure to perform insulation work for all drainage piping in order to prevent any possible
water drop due to dew condensation.
(7) Apply the suitable diameter for converging drainage pipe according to the operating capacity
of the unit.
① -drainage pipes assembled by T-shaped joints
(8) The installation height of raising pipe for drainage should be lower than 850mm. The gradient
from raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe is
vertical with the unit, the raising height should be less than 800mm.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
insulating
pipe
Fig 4.3.1
Fig 4.3.2
10
drainage pipe
of indoor unit
insulating tape
(provided))