Download Print this page

Technician Setup - Pro1 Technologies T731W Installation Manual

Advertisement

Wiring
Base Module - PTAC Installation
Range between the thermostat and the base module is up to 100 feet
with no obstructions and up to 50 feet through standard building
materials. To optimize the range try placing the base module with no
metal between it and the thermostat.
The base module is designed to be mounted behind the front grille
of a packaged terminal air conditioner (PTAC). Refer to the PTAC
manufacturer's manual for instruction to remove the front grille.
Check clearance to ensure the fit of front grille after base module
installation. See below for a few location recommendations.
Front Mount:
Inside PTAC
Housing
7
Wiring
Typical 1H/1C System: 1 Speed Fan
R
COMPRESSOR
Y
RELAY
W
HEAT RELAY
C
GL
FAN RELAY
GH
Typical 1H/1C Heat Pump System: 2 Speed Fan
R
COMPRESSOR
Y
RELAY
W
C
GL
FAN LOW RELAY
GH
FAN HIGH RELAY
O/B
CHANGE OVER
VALVE
Typical 2H/1C Heat Pump System: 2 Speed Fan
COMPRESSOR
RELAY
AUX HEAT
RELAY
FAN LOW RELAY
FAN HIGH RELAY
CHANGE OVER
VALVE
11
Side Mount:
Inside PTAC
Housing
C
L2
L1
R
C
L2
L1
R
O
B
COOL CHANGE
OVER VALVE
HEAT CHANGE
OVER VALVE
C
L2
L1
R
O
B
COOL CHANGE
OVER VALVE
HEAT CHANGE
OVER VALVE
When Working With A Vertical Unit
1. Do not mount Module inside the cabinet of the unit, or in a
metal enclosure.
2. Mount on the outside of the unit to maximize wireless
communication.
When Working With A Metal Sleeve Cabinet, Room Cabinet,
or PTAC Cover
1. If cabinet has open bottom, mount the module just inside the
cabinet as close to the open bottom as possible without placing it in
danger of being bumped or touched by furnishings, vaccum, etc.
2. Another good module location would be on the underside of the
top of the cabinet or cover. Directly behind the open Louver/Grill.
Chasis
Front Panel
1. Set the thermostat system switch to OFF.
2. To enter Tech Setup Menu, press and hold
3. Use
or
to select desired setting for each option.
4. Tap
and
together to move next option.
5. To exit Tech Setup Menu, move system switch or wait 15 seconds.
Important Tech Setting Notes
1. Tech settings must be transferred to the basemodule.
2. The transfer happens automatically when you exit the tech menu.
3. The Screen will display "TEC SET OK" when the basemodule has received the
new tech settings.
Tech Setup Steps
This feature allows the installer to
Room
change the calibration of the am-
bient room temperature display.
Temperature
For example, if the thermostat
Calibration
reads 70 degrees and you would
like it to read 72 then select +2.
The swing setting, often called
"cycle rate", "differential" or "antic-
ipation" is adjustable and dictates
how frequenlty the system cycles
Cooling
on and off. For example: A swing
setting of 0.8˚ will turn the
Swing
cooling on at approximately 0.8˚ 
above the setpoint and turn the
cooling off at approximately 0.8˚ 
below the setpoint.
The swing setting, often called
"cycle rate", "differential" or "antic-
ipation" is adjustable and dictates
how frequenlty the system cycles
Heating
on and off. For example: A swing
setting of 0.8˚ will turn the
Swing
heating on at approximately 0.8˚
below the setpoint and turn the
heating off at approximately 0.5˚ 
above the setpoint.
Rough-In
Wall Opening
Sleeve Cabinet

Technician Setup

and
together for 3 seconds.
LCD Will Show
Adjustment Options
4 ˚ - -4 ˚
CALIBRATE
0.2 ˚ - 2 ˚
0.8
COOL SWING
0.2 ˚ - 2 ˚
0.8
HEAT SWING
Wiring
8
Default
0˚F
0.8˚
0.8˚
12