AGF Manufacturing Inc. Model 5500 COLLECT DRAIN ® The COLLECT DRAIN Model 5500 is a heated and insulated auxiliary drain ® (condensate collector/drum drip) with a programmable logic control (PLC), which enables fully automatic or on demand push-button operation. The Model 5500 is designed for installation in climates where freezing or below freezing temperatures are present and result in the failure of typical collectors.
Power Lamp, Single Flash Malfunction, heater has been continuously operating for at least two (2) hours. Power Lamp, Double Flash An auto drain cycle has been performed. AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.agfmfg.com...
3. Connect another pair of wires to the top of the RB1 and RB2 (remote button) terminals. 4. Connect these wires to the appropriate place in the Remote Panel. AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.agfmfg.com...
The default setting of 50º F is adequate for outside temperatures down to 0º F. If operating below this temperature, the set- point should be increased. Consult AGF for set-point guidelines. 9. Close the M5500 electrical enclosure cover and secure latch with a slotted screwdriver.
50º F is suitable for conditions down to 0º F. Consult with AGF for recommended settings if operating the M5500 in an area below 0º F. The thermostat controls the heater operation to within approximately ±10º F of the set-point (i.e.
Model 5500 COLLECT DRAIN Owner’s Manual ® Est. Daily Power Consumption 2.00 1.80 1.60 1.40 1.20 1.00 0.80 0.60 0.40 0.20 0.00 Average Ambient Temperature (°F) Power consumption of the M5500 is based on several factors including ambient temperature, humidity, installation location and exposure to sunlight. The following graph shows an estimation of the daily energy consumption verses the ambient temperature when the set-point is 50º...
Page 9
First, ensure power to the system is turned off. Then, pull up on the blue knob located on the actuator cover until it clicks and turn the knob until the desired valve position is reached. AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.agfmfg.com...
Model 5500 COLLECT DRAIN Owner’s Manual ® Drain Override: WARNING: The following feature is for use ONLY when servicing the sprinkler system and system has been taken offline. The Drain Override will fully open the auxiliary drain causing the sprinkler system to activate if it has not already been depressurized.