Important Installation Information - Honeywell PENA D MLS2000SSP Installation And Commissioning Instructions

Table of Contents

Advertisement

Available languages

Available languages

GB
Note:
D HP2000 required for commissioning.

Important installation information!

Installation and commissioning may only be done by an authorised
electrician. Mains power (230V~/50 Hz) to electrical equipment
must be switched off during installation. Applicable laws and
standards of the country in which the device is operated must be
observed!
MLS Digital Scene Select Panel D MLS2000SSP
Dimensions
ON
1
2
3
5
6
OFF
4
144mm Module
146mm Fascia
Note:
The module's enclosure and its supporting frame are designed to
attach to the front of any standard Two-Gang Box, sinking, dry-
lining or surface mounting, with a minimum depth of 30mm.
Connection
L N
D MLS2000SSP
MLS2000SSP Mk2
~
230V
50Hz.
Power consumption <10W
ta 0.. 40 C
o
MAINS INPUTS
Please read instructions prior to installation.
Novar ED&S Ltd
Haydock Lane, Haydock
Merseyside. WA11 9UJ
Tel: 01942 719229
Fax: 01942 272767
DIRECTION OF CABLE INSERTION
WARNING:
UNDER NO CIRCUMSTANCES SHOULD MAINS POWER (e.g. 200-
250V ~) BE APPLIED TO THE MLS BUS CONNECTIONS OR THE
DIGITAL DIMMING OUTPUT CONNECTIONS. THIS WILL CAUSE
DAMAGE AND COULD BE HAZARDOUS.
It is imperative that the MLS bus is wired with the correct type
of cable. Normally it should be 1.5mm
Please read Application Note AN4001 for more details.
Two-core mains-rated cable is recommended for the dimming
signal (see Note 3 in right column). The dimming control output
should be connected only to the control inputs of ballasts - never
to a detector.
The supporting frame of the module must be earthed, via its earth
terminal, to render the metal fascia safe.
PEHA Lichtsteuerung – PEHA Elektro GmbH & Co. KG a Honeywell Company · Gartenstraße 49 · 58511 Lüdenscheid · Deutschland · www.peha.de · peha@peha.de
82mm
86mm
TOP
DIGITAL
MLS BUS
VIEW ON REAR OF
OUTPUT
POLARITY
POLARITY
MODULE ENCLOSURE
FREE
FREE
BOTTOM
unscreened twisted pair.
2
Important Additional Notes
1. All terminals on this product are provided for final connection.
It is not intended that the product be used as a junction box for
looping cables.
2. A means of disconnection must be incorporated in the fixed
wiring in accordance with the current wiring regulations.
3.The dimming signal, while nominally 12V, should not be treated
as SELV as its 0V line (D1 above) is close to Mains Neutral
potential.
Installation
The suggested installation procedure is as follows:
a) Fit the double-gang sinking box at the desired location (minimum
box depth 30mm).
b) Pull through mains power cable, MLS bus cable and digital
dimming cable (if required), observing wire requirements and
regulations.
c) Connect to the terminal block at the rear of the module, observing
correct terminations and cautionary notes.
d) Fix module's supporting frame to back box.
e) Clip the fascia plate onto the module's supporting frame.
Please note that the flat head countersunk screws supplied with the
unit must be used in order to ensure proper fit of the fascia plate.
If the application requires longer screws, M3.5 extension studs
should be used.
Commissioning – Using the D HP2000
Once installation is complete, it is necessary to programme the
panel's parameters - as with detectors, this is done using the D
HP2000 Programmer.
In order to work harmoniously with detectors controlling lumi-
naires within the same space as, and linked by zone to, the lumi-
naires directly controlled by the MLS Scene Switch Panel, the Off
Delays configured in the detectors and in the MLS Scene Switch
Panel should be of the same duration.
It is important that the D HP2000 be held perpendicular to, and at a
distance of between 0.5m and 2m from, the panel.
1. Switch on the D HP2000 by pressing the red button.
2. Point the D HP2000 at the panel and press the DOWNLOAD
button. The D HP2000 will confirm the product's identity and
call up the correct menu of parameters and their current settings.
3. Use a combination of UP, DOWN, FORWARD and BACK buttons
to navigate the parameter menu, selecting the options for each
shown. (See Tips below.)
4. When complete, aim the D HP2000 at the panel and press the
UPLOAD button. To acknowledge a successful programming
operation, the HP2000 displays „DATA OK".
5. After a short period of inactivity (default 5 minutes) the D
HP2000 hibernates retaining the most recent settings.