Refrigerant sensor for industrial applications

Advertisement

3
Operation
Modes of Operation
C
TM
The Manning AirScan
operation and calibration:
Normal run mode with output filtering
Normal run mode without output filtering
4/20 mA loop check
4/20 mA calibration to an external PLC or
read-out panel
Neutral gas resting point or "zero" calibration
mode
Span calibration modes
Normal Run Modes
Normal run mode with output filtering
This mode outputs a signal from 4 to 27 mA with a
"dead band" from 4 to 4.6 mA. This "dead band"
masks small environmental anomalies that could
facilitate output signal fluctuations or transients
around the 4 mA resting point when the unit is not
sensing target gas.
Start: If the "system" LED is blinking slowly, press
and hold both S1 and S2 simultaneously for 1 second
or more until the "system" LED is continuous ON,
then release both buttons. If the "system" LED is
blinking fast, this mode cannot be engaged and the
factory needs to be contacted. See the following
example.
LED
SEQUENCE
POWER
G
Y
SYSTEM
Y
CALIBRATE
FAULT
R
mA FAULT
R
SOURCE
G
ATMOS
G
Manning AirScan-iR Refrigerant Sensor
continued
iR has various modes of
OFF
OFF
OFF
N/A
19100 AirScan-iR-ind 05/2006 REVA Copyright © 2006 Manning Systems, Inc. All Rights Reserved.
Normal run mode without output filtering
This mode outputs a signal that nominally rests at 4
mA and can range continuously from 0 to 27 mA. Any
subtle changes in sensor response will be sent to the
mA loop output. This mode is entered automatically
when the calibration modes are activated. Some users
may wish to see the subtle anomalies in the signal
near the nominal 4 mA rest area.
Start: If the "system" LED is continuous ON, press
and hold both S1 and S2 simultaneously for 1 second
or more until the "system" LED is blinking slowly then
release both buttons to enter this mode. If the
"system" LED is blinking fast this mode is always
engaged and can only be exited by fully calibrating
the unit. See the following example.
LED
SEQUENCE
POWER
G
SYSTEM
Y
Y
OFF
CALIBRATE
R
OFF
FAULT
OFF
mA FAULT
R
SOURCE
G
ATMOS
G
N/A
12