Verasys LC-ZEC510 Series Quick Start Manual

Verasys LC-ZEC510 Series Quick Start Manual

Hide thumbs Also See for LC-ZEC510 Series:

Advertisement

Manufacturer
Default direction to close
Titus
Counterclockwise
Tuttle and Bailey
Counterclockwise
Table 1: Quickfill defaults
Box
Area
Pickup gain
Duct
ETI
ETI
Krue
Size
with
with
ger
a
a
45°
90°
Rota-
Rota-
tion
tion
4
0.09
1.71
1.63
2.32
5
0.14
1.69
1.66
2.31
6
0.20
1.67
2.90
2.32
7
0.27
N/A
N/A
2.32
8
0.35
1.61
2.52
2.33
9
0.44
N/A
N/A
2.33
10
0.55
1.63
2.41
2.32
12
0.79
1.61
2.38
2.32
14
1.07
1.59
2.29
2.33
16
1.40
1.61
2.29
2.33
18
N/A
1.59
2.43
N/A
19
N/A
N/A
2.92
N/A
20
0.78
1.61
N/A
N/A
22
0.78
1.60
2.65
2.33
24
N/A
N/A
N/A
N/A
26
1.00
N/A
N/A
N/A
30
N/A
N/A
N/A
N/A
40
2.67
N/A
N/A
N/A
Part No. 24-10143-01779 Rev. —
Additional information
Refer to the Verasys System Operation Overview Techni-
cal Bulletin (LIT-12012370) for more information about the
control parameters and their various sequences.
For additional information about Verasys, use the QR
code or visit www.verasyscontrols.com.
Tuttle
Titus
and
Bailey
European single point of contact: NA/SA single point of contact:
2.80
1.63
JOHNSON CONTROLS
WESTENDHOF 3
3.00
1.95
45143 ESSEN
GERMANY
2.90
3.07
3.00
2.57
APAC single point of contact:
2.90
2.39
JOHNSON CONTROLS
N/A
2.30
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
3.00
2.31
WUXI JIANGSU PROVINCE 214142
CHINA
3.00
2.76
3.00
2.02
3.00
2.12
3.00
N/A
N/A
N/A
N/A
2.19
3.00
2.19
*241014301779-*
N/A
N/A
N/A
2.57
3.00
N/A
N/A
2.22
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
24-10143-01779 Rev. —
(barcode for factory use only)
© 2018 Johnson Controls.
ZEC510 VAV
Controller
QUICK START GUIDE
Part No. 24-10143-01779, Rev.—
Issued September 2018
LC-ZEC510-x

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LC-ZEC510 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Verasys LC-ZEC510 Series

  • Page 1 Additional information Manufacturer Default direction to close Titus Counterclockwise Refer to the Verasys System Operation Overview Techni- ZEC510 VAV cal Bulletin (LIT-12012370) for more information about the Tuttle and Bailey Counterclockwise control parameters and their various sequences. Controller Table 1: Quickfill defaults For additional information about Verasys, use the QR code or visit www.verasyscontrols.com.
  • Page 2 Unoccupied Heating Min Flow: Sets the minimum troller uses the outputs to control the heat in the VAV Krueger Counterclockwise supply airflow of the VAV box when in unoccupied box. Refer to the Verasys ZEC510 VAV Installation Instructions (Part No. 24-10143-01760) for important product application information.

This manual is also suitable for:

Zec510 vav