Advertisement

Quick Links

ZEC410 VAV Controllers
Installation Instructions
LC-ZEC410-xx
Applications
The ZEC410 VAV Controllers are components of the Verasys SMART equipment family. The VAV Zone controllers run
a pre-engineered HVAC zoning sequence and provide the inputs and outputs required for this application.
The ZEC Controller contains multiple features to ensure occupant comfort. Optional occupancy sensing capability
enables the ZEC controller to switch from occupied mode to standby mode based upon zone activity. Standby mode
maximizes energy savings by using setpoints that are higher and lower than occupied mode setpoints.
The ZEC410 controller also uses plug and play technology to detect which network sensor types are connected. See
the Accessories section to determine availability of additional sensing product information.
You use the Verasys Smart Building Hub to set up the ZEC410 controller. The VAV controller commissioning is
performed with either the Smart Building Hub or the VAV Balancing Thermostat.
IMPORTANT: Use this ZEC410 VAV controller only as an operating control. Where failure or malfunction of the
PEAK OEM controller could lead to personal injury or property damage to the controlled equipment or other
property, additional precautions must be designed into the control system. Incorporate and maintain other
devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against
failure or malfunction of the ZEC410 VAV controller.
IMPORTANT : Utiliser ce ZEC410 VAV Controller uniquement en tant que dispositif de contrôle de
fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du controller risque de provoquer des
blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de
contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon
permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de
sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de
dysfonctionnement du ZEC410 VAV controller.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential
area may cause harmful interference, in which case users will be required to correct the interference at their
own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Contents subject to change.
Refer to the
QuickLIT website
ZEC410 VAV Controllers Installation Instructions
1
Part No. 24-10143-1264, Rev. –
Issued January 2017
for the most up-to-date version of this document.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZEC410 and is the answer not in the manual?

Questions and answers

Summary of Contents for Verasys ZEC410

  • Page 1 The ZEC410 controller also uses plug and play technology to detect which network sensor types are connected. See the Accessories section to determine availability of additional sensing product information.
  • Page 2: Installation

    Mount the ZEC so that the enclosure walls do not obstruct cover removal or ventilation through the controller. • Mount the ZEC so that the power transformer and other devices do not radiate excessive heat to the controller. ZEC410 VAV Controllers Installation Instructions...
  • Page 3 Used for BACnet reserved function devices - not used for Verasys System Bus controllers Address used by an FC Bus or System Bus - connected to a Smart Building Hub - not used for Verasys System Bus controllers or BACnet device address...
  • Page 4 12. Push the Manual Override button, and turn the actuator coupling manually to ensure that the actuator can rotate from full-closed to full-open positions without binding. 13. Complete the mounting by rotating the damper to the full-open position. ZEC410 VAV Controllers Installation Instructions...
  • Page 5: Input And Output Terminals

    See Figure 8 for an example of the staged control wiring. See Figure 9 for an example of the incremental control wiring. Sensor Actuator (SA) Bus Terminal Block The SA Bus terminal block is a brown, removable 4-terminal plug, that is keyed to only fit into the board-mounted brown SA bus. ZEC410 VAV Controllers Installation Instructions...
  • Page 6 The modular SA Bus ports provide a connection for the VAV Balancing Tool. The FC Bus port is not used in ZEC installations. Figure 5: Pin Number Assignments SA and FC Bus Ports Power (15 VDC) Bus and Power Common Power (15 VDC) Bus and Power Common SA or FC Bus SA or FC Bus + ZEC410 VAV Controllers Installation Instructions...
  • Page 7 You may damage the controller by sharing power with other devices. To wire the ZEC410 controller: 1. Terminate wiring according to Figure 8 if you are using staged outputs for the heating control. See Figure 9 if you are using incremental outputs for the heating control.
  • Page 8 5. Connect the ZEC controller to 24 VAC, Class 2 power. Figure 7: ZEC410-1 Controller - VAV with Staged Reheat Control Wiring Example VAV with No Fan DA-T ZEC410-1 (Optional) HTG1-C (Optional) HTG2-C (Optional) HTG3-C (Optional) SUPHTG1-C (Optional) ZN-CO2 ZN-T...
  • Page 9 Figure 8: ZEC410-1 Controller - VAV with Staged Reheat Control Wiring Example CONFIGURABLE BINARY Addres See Riser Diagram ZEC410 VAV Controllers Installation Instructions...
  • Page 10 (CO ). The reset of the damper minimum flows do not exceed the maximum value that you set. the CO sensor with the highest value determines the reset, if more than one is wired. ZEC410 VAV Controllers Installation Instructions...
  • Page 11 Figure 9: ZEC410-2 Controller - VAV with Incremental Reheat Control Wiring Example VAV with No Fan VAV with Parallel Fan DA-T ZEC410-2 (OPTIONAL) DA-T (Optional) ZEC410-2 (OPTIONAL) (Optional) SF-C RETURN SEE HEATING RETURN VALVE DETAILS SEE HEATING BELOW VALVE DETAILS...
  • Page 12 (CO ) setpoint. The reset of damper minimum flows does not exceed the maximum value you set. The CO sensor with the highest value determines the reset if more than one sensor is wired. ZEC410 VAV Controllers Installation Instructions...
  • Page 13 24V HOT ZEC410-3 NETSTAT IS SELECTED ) CONNECTOR ON BACK OF SENSOR SA PWR SA PWR SA PWR ZONE SENSOR ZN -CO2 CONNECTOR ON BACK OF SENSOR 24V HOT 24V Hot (OPTIONAL) 24V COM 24V Com ZEC410 VAV Controllers Installation Instructions...
  • Page 14 Run all low-voltage wiring and cables separate from high-voltage wiring. • All FC and SA Bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire. • Shielded cable is strongly recommended for all FC and SA Bus cables. ZEC410 VAV Controllers Installation Instructions...
  • Page 15: Setup And Adjustments

    21, set Switch 16 to ON first, then set Switch 4 ON, followed by Switch 1 (16+4+1=21). 3. Set a unique and sequential device address for each of the field controllers connected on the System Bus or Zone Bus, starting with device address 6. ZEC410 VAV Controllers Installation Instructions...
  • Page 16: Operation

    Balancing Sensor or the Zone Setup screen on the Verasys System Smart Building Hub. For detailed information on Verasys System, including dehumidification capability, DCV, occupancy sensing, and general operating modes, refer to the Verasys System Operation Overview Technical Bulletin (LIT-12012370).
  • Page 17: Occupancy Sensor

    You can enable the occupancy sensor in the Zone Setup screen of the System Manager or Zone Coordinator. You can set occupancy sensitivity and time delay until standby locally at the sensor. Refer to the Verasys System User’s Guide (LIT-12012371) for more information.
  • Page 18 If you are using one transformer to power multiple devices, verify that the device 24 VAC power connection follows the polarity of the common and 24 V terminations (see System and Zone Bus Supply Power Wiring Guidelines). • Check for opens and shorts • Check terminations ZEC410 VAV Controllers Installation Instructions...
  • Page 19: Repair Information

    Note: Values may fluctuate due to ongoing communications; this operation is normal provided the voltage is within the defined range. Repair Information If the ZEC410 controller fails to operator within its specifications, replace the unit. For a replacement unit, contact the nearest Verasys representative. Technical Specifications...