TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TX7-X Operating Manual

TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TX7-X Operating Manual

Multixplo and multitox detectors

Advertisement

Quick Links

MULTIXPLO AND MULTITOX
DETECTORS
DG-TX7-X (Catalytic)
DG-TT7-K (Catharometer)
(with Magnetic interface)
OPERATING MANUAL
NOSP17665-Revision 02a

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Everywhereyoulook DG-TX7-X and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TX7-X

  • Page 1 OPERATING MANUAL MULTIXPLO AND MULTITOX DETECTORS DG-TX7-X (Catalytic) DG-TT7-K (Catharometer) (with Magnetic interface) NOSP17665-Revision 02a...
  • Page 2 User manuals in other languages are available on Website https://teledynegasandflamedetection.com Copyright  January 2021 by TELEDYNE OLDHAM SIMTRONICS S.A.S. All rights reserved. No reproduction of all or part of this document, in any form, is permitted without the written consent of TELEDYNE OLDHAM SIMTRONICS S.A.S.
  • Page 3 SIMTRONICS, even though they may be involved in the sale of TELEDYNE OLDHAM SIMTRONICS products. TELEDYNE OLDHAM SIMTRONICS shall not be responsible for any direct or indirect damage, or any direct or indirect consequence, resulting from the sale and use of any of its products UNLESS SUCH PRODUCTS HAVE BEEN SELECTED BY TELEDYNE OLDHAM SIMTRONICS ACCORDING TO THE APPLICATION.
  • Page 4 The use of the unit has been projected for the applications specified in the technical characteristics. Exceeding the indicated values cannot in any case be authorized. TELEDYNE OLDHAM SIMTRONICS recommends regular testing of fixed gas detection installations (read Chapter 7.2).
  • Page 5: Table Of Contents

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Table of Contents 1 Product description ................1 Application Fields ....................1 DG-TX7-X ....................... 2 DG-TT7-K ........................ 2 Technical specifications ................. 2 Detection Cartridge ..................4 Communication Interface ................4 Product Code ..................... 6 2 Technical features ................
  • Page 6 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.11 Magnets operation ................... 45 7 Maintenance ..................47 Power off / opening of housing ..............47 Periodic maintenance ..................47 List of main faults ....................48 Replacing the cartridge ................. 49 Replacing the complete detector ............. 50 8 ATEX / IECEx Marking ..............
  • Page 7: Product Description

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Product description The DG-TX7-X is designed to monitor explosions risks induced by the presence of flammable gases or vapours (hydrogen, hydrocarbons, alcohol, etc.). The DG-TT7-K is designed to monitor the gas concentration in %vol. induced by the presence of some special gases or vapours (hydrogen, helium, carbon dioxide, etc.).
  • Page 8: Dg-Tx7-X

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL DG-TX7-X Detectors are calibrated on 100% LEL (Lower Explosive Limit) of a particular-gas or vapour. The DG-TX7-X is a MultiXplo detector based on a thermo-catalytic oxidation transducer, which requires oxygen to function properly. In the event of a long period without oxygen, the measurement will no longer be representative of the concentration of gases or vapours.
  • Page 9 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL This cartridge is connected to the detector’s body by an open ring leaving the label visible. A coloured ring enables the identification of the device type at a larger distance. • A metallic support cable (optional) connects the wall mounting support and the housing, making the maintenance easier.
  • Page 10: Detection Cartridge

    OPERATING MANUAL Detection Cartridge Detection Cartridges are explosion proof designed. They are common to all TELEDYNE OLDHAM SIMTRONICS MultiXplo and MultiTox-K products in order to reduce the number of spare parts. • DG-RX7-X et DG-RT7-K: Network « Télécapteur » line •...
  • Page 11 C, in HART configuration (H):DGi-**7-****-**H-**-***-*-C-* TELEDYNE OLDHAM SIMTRONICS devices under HART protocol enable the use of all the functions available with the TLU600 via the HART terminal See the document D1401002 for the using of Hart terminal TLH700 (the Detector Device Descriptor must be downloaded).
  • Page 12: Product Code

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Product Code Product codes are created from functional codes: DG-**7-****-***-**-***-*-*-* Detector type -00J Compact Sensor Télécaptor Network version Replacement cell Accessories Families Toxic Flame Flammable gas None Version BT606 housing BT10 housing Gas type Refer to gas matrix Measurement range Refer to gas matrix...
  • Page 13 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL -00J Cartridges No cartridge or not specified or flame Electrochemical type M DGi-TT7-O / Dmi-TT6-O Electrochemical type G Electrochemical type Y Dgi-TT7-E / Dmi-TT6-E / DGi-TT7-O / Dmi-TT6-O Electrochemical type N DG-TT7-X / DM-TT6-X Catalytic Semi-conductor (general designation for semiconductor type DG-TT7-S / DM-TT6-S...
  • Page 14 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL -00J Language Fr / GB French English Portuguese Chinese Hardware version Type 63 Type 65 Type 67 (HART) Type 69 (magnet) Software version Standard NOSP17665 Revision 02a...
  • Page 15: Technical Features

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Technical features GENERAL Type Gas detector DG-TX7-X MultiXplo (catalytic gas detector) DG-TT7-K MultiTox (catharometer gas detector) DG-RX7 or DG-RT7 Network detector Calibration Recommended test every 6 months OUTPUT SIGNALS 4-20mA loop signal Type active (source) maximum load impedance 700Ω E version - «...
  • Page 16 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL ELECTRICAL Power supply: 24VDC,(18 – 28 V DC versions DG-T#7) (18 – 35 V DC versions DG-R#7)) Consumption: 1.6 W typical, 5 W maximum 3 W typical, 5 W maximum for network detector Wiring: 0,5mm²...
  • Page 17 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL EXPLOSION PROOF HOUSING Material stainless steel 316 L Weight 4.0 kg stainless steel ATEX/IECEx Please refer to §8 DIMENSIONS Figure 2: Outline drawing (mm) (Version with SX202: height dimensions = 190 mm) NOSP17665 Revision 02a...
  • Page 18 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 19: Performances

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Performances Expected lifetime in standard conditions: • >5 years for DG-TX7 • >10 years for DG-TT7-K This lifetime can be reduced in case of exposure to dusty environments. For catalytic version, some compounds are known to poison sensors. These include, organometallic, silicone and some halogenated compounds DG-TX7-X DG-TT7-K...
  • Page 20 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL  Measured at 50% LEL of the considered gas  In % full scale  On the range: -10°C to +40°C. (In years) Expected values based on “typical” site operating conditions without poison or corrosive compounds.
  • Page 21: Installation

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Installation The detectors described in this manual are safety instruments intended to be installed in explosive atmospheres and have been designed in compliance with standards EN60079-0 and EN60079-1, EN 60079-29-1, CEI 60079-0 and CEI 60079-1. Intervention in some sites may be subject to restrictions that we invite you to follow for your own safety and those of others.
  • Page 22 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL When mounting the cable gland (optional), if no tightening torque is specified by the manufacturer, consider than a tightening torque of 20N.m +/-10% is the most suitable. On stainless steel housings, plugs are sealed with Loctite. If the plugs are moved or removed, it must be sealed again, using Loctite or equivalent.
  • Page 23 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 4.2.2 Cable inputs Connection cables must pass through a cable gland (Explosion Proof certified) as an option For installation details, refer to the instructions provided by the manufacturer of the cable gland used. The unassigned cable glands entries must be blanked with explosion proof tubétanche 577 certified plugs (M20).
  • Page 24: Electric Connection

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 4.2.4 Magnets identification The magnets are identified by two stickers “PG1” and “PG2” fixed on the housing. Electric Connection Never adjust electrical connections when detectors are powered. Maintenance must be undertaken by qualified staff. Observe safety site rules. The MultiXplo and MultiTox are sensors with standard current output 4-20mA or 0-22mA.
  • Page 25 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 4.3.1 Connection of the electrical ground braid Use a shield connection clamp (not supplied) to connect the shielding of the cable to the electric ground of the housing (see § below). 4.3.2 Grounding A M4 screw passes through the body of the enclosure, enabling the electronic ground of the housing to be connected to the local ground.
  • Page 26 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Terminal blocks : Point JP11 Description 0 V retour +24VDC power supply +24VDC power supply loop (connected to point 2) 0 V, connected to point 1 20mA loop : input 20mA loop : output 4.3.3.1 3-wires connection (source) Detector...
  • Page 27 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL The 20mA current loop must be supplied with a PLC. The current return must be connected to the 0V at the level of the L- terminal. To proceed, please connect the 4 (V-) and 6 (L-) terminals at the terminal block level of the device.
  • Page 28 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Re la y c a rd , te rm in a l b lo c k (o p tio n ): Point Description Relay 1 common Relay 1 de-energized Relay 1 energized Relay 1 energized Relay 2 common Relay 2 common Relay 2 de-energized...
  • Page 29 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Maintain a 10mm minimum gap between the resistor and the terminal block or any other neighboring parts. The R1 value is given as an indication. It must comply with the following conditions: • Minimum consumption = 5 Watts •...
  • Page 30 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL The connection of power supply wires (4 on side A and 4 on side B). • Two red wires on V +: +24 V • Two white wires on V-: 0 V Connection of the media wires (2 on side A and 2 on side B) •...
  • Page 31 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL In order to operate this analog input, an additional electronic card (PIE 3508 or PIE 3509) is added above the numeric card The hosted sensor NEEDS to get its own power The connecting wires to another detector are limited to a 1 mm² section. Using this board leads to a connection between 0V from power supply and housing ground 4.3.8...
  • Page 32: Detection Cartridge

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL The table below shows the maximum cable lengths based on the wire cross section: Min. single wire cross section mm²/AWG 0,5 (20) 0,9 (18) 1,5 (16) 2.5 (13) Maximal Length 15 m 30 m 50 m Detection cartridge The cartridge is separated from the detector to enable its replacement.
  • Page 33: Commissioning

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Commissioning Visual inspection Make certain that all the operations of the “Installation” chapter have been achieved correctly. Pay particular attention on installation conformity, check the cables entry, the presence of O- rings, and the connection of the cartridge. •...
  • Page 34 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 35: Operation

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Operation Environmental conditions The lifetime of the catalytic cartridge depends on the operating environment related to certain pollutants. Take care to avoid exposures to some vapours products as silicone (vapours of some paintings, some seals ...), halogenated products (molecules containing one atom of chlorine, fluorine, bromine) or as sulphur ones (H2S...).
  • Page 36: Signal Current Loop

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Signal current loop “4-20” “0-22” Display TLU state State [mA] [mA] Line fault yellow Backlight Configuration fault yellow Backlight Detector fault (electronic) yellow Backlight Measure fault yellow Backlight Warming-up Start inhibition violet Backlight remaining time including power up Permanent inhibition...
  • Page 37: Alarm Indication

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Display time: The detector displays concentration or status. Depending on events, the detector displays cyclically important information according to the context: unit, gas, label, fault, alarms, inhibition and the time remaining inhibition…. Output current (4-20mA ou 0-22mA) : It can be modified by the user.
  • Page 38 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Normal operating mode: The digital readout provides the following information: • Concentration • Measuring scale • Abbreviation of the gas used • Label of the device In case of alarm: • The display of concentration flashes •...
  • Page 39: Wireless Communication Tool Tlu600

    All settings and tests of detectors can be done by the wireless communication tool TLU600. This communication tool and its software are compatible with all TELEDYNE OLDHAM SIMTRONICS detectors: MultiFlame, MultiTox and MultiXplo. Communication is made via infrared link (IrDA), similar but more efficient than infrared links for computers.
  • Page 40 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Main screen displays identity and state of the detector. 6.6.2 General operation The user can navigate through the menu with the F1 to F4 keys, whose functions change depending on the fields displayed above each key. Standard functions: •...
  • Page 41 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Menus displayed without access code Menus displayed with relay board Menus displayed with Syntel board Menus not displayed with Syntel board NOSP17665 Revision 02a...
  • Page 42: Information Menu [Info]

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Information menu [INFO] The information menu contains all information concerning the identity and settings of the detector. The first screen gives the detector’s reference and its serial number. 6.7.1 [IDEN]tity submenu Presentation of: • The serial number •...
  • Page 43: Adjustment Menu [Adjt]

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Mode screen The first line shows the operating mode of the sensor in the network (logic link test/out of order/emulation). The second line shows if the network part of the detector is “operating” or “out of order”. For any further details, please refer to the Syntel system operating manuals.
  • Page 44 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.8.2 [CAL]IBRATION sub-menu 6.8.2.1 Zero-point setting The operator can set the zero point with the wireless communication tool TLU600. The detector is in maintenance inhibition mode for 10 minutes after it goes back to main screen. Use the setting menu and validate the INH command for acknowledgement.
  • Page 45 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.8.2.2 Calibration Calibration must be made with the gas the detector is set to detect, with the SET menu (F2 key) of the wireless communication tool TLU600 and a calibration kit. The calibration gas should be injected at a flow rate between 30 l/h and 60 l/h.
  • Page 46 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.8.3 [DISP]LAY sub-menu This menu gives access to the light intensity setting of the backlight and display: • AUTO: Automatic adjustment depending on the lighting environment • Level 0: Backlight is switched off, minimum display •...
  • Page 47 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.8.6 [SORT] Output configuration sub-menu 6.8.6.1 Relays configuration This menu gives access to the configuration of the relay operating mode and to conditions of activations. This menu is available only with the optional relay card State of the relays: Each relay can be configured: •...
  • Page 48 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Contacts are then described as below: Relay 1 Relay 2 Relay 3 Detector status “Fault” “Alarm” “Alarm” Normal C1-T1 closed C2-T2 open C3-T3 open (no alarm, no fault, no inhibition C1-R1 open C2-R2 closed C3-R3 closed and detector powered) C1-T1 closed...
  • Page 49: Maintenance Menu [Main]

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.8.8 Sous-menu [NEG] Concentration négative The detector can display the negative concentration. There is no sense from a point of physical view but it allows to prevent a zero drift and to have a preventive maintenance before the zero drift fault.
  • Page 50: Ambiguity Function In Combustible Gas Detector Smart Sensors

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.10 Ambiguity function in combustible gas detector smart sensors In compliance with applicable standards, the ambiguity function is activated when a detected gas concentration rises above 120% LEL. The signal is locked at 21.7 mA to protect against any false measurement due to oxygen deficiency.
  • Page 51: Magnets Operation

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL 6.11 Magnets operation The digital display gives access to different menus. To enter in these menus, the wand has to put in place on the stickers “PG1” or “PG2”. The user must maintain the wand on the magnets with time longer or shorter depending on the desired function.
  • Page 52 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Menus not available with Syntel card Menus available with relay card Menus available without access code NOSP17665 Revision 02a...
  • Page 53: Maintenance

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Maintenance The interventions described in this chapter must be performed by competent and qualified staff. Device performances may be affected if the present instructions are not respected. Cartridge unplug or device opening imperatively require power to be OFF Zero adjustment does not affect the sensitivity of the detector and vice versa.
  • Page 54: List Of Main Faults

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL If the detector enters in ambiguity mode, a test of the zero point and a gas test are recommended. We recommend cleaning the communication head window at the same time. For any other operation, please contact your supplier or our technical services. 7.2.2 Corrective maintenance If the detection unit or the PLC signals a detector’s fault, the detector must be tested directly with...
  • Page 55: Replacing The Cartridge

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL FAULTS CAUSES SOLUTIONS Non-memorized fault. Automatic DRIFT_FAULT Sensor drift: the measure is acknowledgement when the measure below -10% goes back above -10%. Resetting the (Zero-point drift) zero point is necessary. Memorized fault, even on a power supply shut down.
  • Page 56: Replacing The Complete Detector

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Replacing the complete detector If the operator needs to replace the complete detector, the easiest way is to take off the main housing from the base of the detector (for more details, refer to § 4.2.1). As the base of the detector remains in place, cable glands do not need to be dismantled.
  • Page 57: Atex / Iecex Marking

    It is also recommended to use the device with the following accessories: AS056-250, AS019, AS015. TELEDYNE OLDHAM SIMTRONICS does not allow any repairs of the flameproof joints and shall not be responsible for any modification of material. NOSP17665...
  • Page 58 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 59: Accessories And Spare Parts

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Accessories and spare parts Accessories Accessories Designation Description Part Number IRDA Remote control Required for adjustments and TLU 600 unit maintenance TLU 600 Remote control unit Avalaible for adjustments and TLH 700 HART maintenance Adapting Plate Used to adapt old detector (BT05- AS049...
  • Page 60 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Accessories Designation Description Part Number Remote calibration Accessory enabling a gas supply AS016  connection tube to be attached near the cartridge. Stainless steel sample For use with gas circuit systems. AS011-2X  flow with 2 ways Duct mounting A series of accessories for installing AS02x ...
  • Page 61: Spare Parts

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Accessories Designation Description Part Number SX202 / MTHX-S screwed on the sensor (external AS205  calibration cup probe only) Magnetic wand Used for setting and maintenance AS055  Detector sensitivity is not modified, response time depend on the flow rate used for injection. A flow rate between 0.5 L/min and 1 L/min should comply with “standard”...
  • Page 62: Gas Table Codes & Range Table Codes

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Storage life of accessories and spare parts : Temperature Humidity Pressure Time TLU600 -20°C to 95% HR (non 1013 hPa +/- 2 ans in +45°C condensable) « clean » atmosphere TLH700 -20°C to 95% HR (non 1013 hPa +/- 2 ans in +60°C...
  • Page 63 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Formula Gas name Comment Range Hexane 2000 ppm Benzene 5000 ppm Toluene 10000 ppm Styrene 3000 ppm Dichloromethane 25 ppm Methane 1 %Vol Methane (Biogas) 2 %Vol Methanol 5 %Vol Chlorine 10 %Vol Carbon monoxide (H2S comp) 20 %Vol Carbon monoxide...
  • Page 64 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Formula Gas name Comment Range Formula Gas name Comment Range Ethyl chloride 500 ppm*m/100 %LEL*m Ethane 1000 ppm*m/100 %LEL*m Acrylonitrile/Vinyl cyanide 5000 ppm*m /100 %LEL*m Dichloroethane Other Propylene oxide Isopropyl alcohol Propyl alcohol Butanol Butadiene Butene Butanal...
  • Page 65 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Regarding reference F2 = DG (100% LEL), the following table defines what TELEDYNE OLDHAM SIMTRONICS uses of correspondence between %vol and 100% LEL. For most of the gases, we use the INRS 2015 data, except for some gases for which we are more conservative (except ammonia and heptane).
  • Page 66 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 67: Conformity Certificate

    MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL Conformity certificate NOSP17665 Revision 02a...
  • Page 68 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 69 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 70 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 71 MULTIXPLO AND MULTITOX DETECTORS OPERATING MANUAL NOSP17665 Revision 02a...
  • Page 72 No. 51 Jinzang Road, TX 77429, 62027 ARRAS Cedex, SHANGHAI Free Trade Zone, FRANCE CHINA Tel.: +1-713-559-9200 Tel.: +33 (0)3 21 60 80 80 Tel.: +86-134-8229-5057 www.teledynegasandflamedetection.com © 2021 TELEDYNE OLDHAM SIMTRONICS. All right reserved. NOSP17665 Revision 02a / January 2021...