For tcxg tubular lead-calcium batteries

Advertisement

Quick Links

®
INSTALLATION
&
OPERATING
INSTRUCTIONS
FOR TCXG TUBULAR
LEAD-CALCIUM BATTERIES
SECTION 93.10G 2014-09
A Division of Exide Technologies

Advertisement

Table of Contents
loading

Summary of Contents for GNB 93.10G

  • Page 1 ® INSTALLATION & OPERATING INSTRUCTIONS FOR TCXG TUBULAR LEAD-CALCIUM BATTERIES SECTION 93.10G 2014-09 A Division of Exide Technologies...
  • Page 2 YOUR GNB INDUSTRIAL POWER REPRESENTATIVE SALESPERSON _________________________________ TELEPHONE ____________________________________ LOCATION _____________________________________ GNB SERVICE ASSISTANCE 1-800-241-4895...
  • Page 3: Table Of Contents

    INDEX Page Page SECTION 1 TABLES 1.0 Safety ..............2 TABLE A ..............4 TABLE B ..............4 SECTION 2 TABLE C ..............5 2.0 Receiving Batteries ........2 STATIONARY BATTERY MAINTENANCE REPORT........7 SECTION 3 3.0 Storage ............2 FIGURES FIGURE 1 ...............4 SECTION 4 4.0 Battery Assembly and Installation ....2 4.1 Site ..............2 4.2 Ventilation ............2...
  • Page 4: Safety

    Before proceeding with the unpacking, request an inspection by the carrier and file a damage claim. handling, installation and operation of a lead-acid storage Also notify your GNB Industrial Power representative. ® battery, the following general information should be reviewed together with the recommended safety precautions.
  • Page 5: Temperature

    4.3 TEMPERATURE and prevent connector heating. If corrosion is observed, DO NOT RE-TORQUE! The connection must be disassembled, A battery location having an ambient temperature of 25°C cleaned, neutralized, and then re-torqued. (77°F) will result in optimum battery life. Batteries operated Install the inter-tier cables as necessary.
  • Page 6: Tables Table A

    SECTION 5 SECTION 6 5.0 EQUALIZING CHARGE 6.0 SPECIFIC GRAVITY An equalizing charge is a special charge given to the battery 6.1 The Specific Gravity (SG) of a fully charged battery is in operation when one of the following conditions exist: 1.215 ±...
  • Page 7: Table C

    100% state of charge. SECTION 10 SECTION 8 10.0 TAP CONNECTIONS GNB advises against tapping portions of the battery as this 8.0 CELL VOLTAGE VARIATION condition may cause unbalanced charging. The untapped portion may get overcharged while the tapped portion may 8.1 Temperature.
  • Page 8: Capacity Testing

    SECTION 13 week, read and record individual cell voltages, connection resistances, specific gravities (corrected to 25°C / 77°F), ambient temperature plus cell temperatures and electrolyte 13.0 Capacity Testing levels for 10% or more of the cells. The cell temperature When a capacity discharge test is desired, it is recommended readings should be taken at each step/tier of the rack to that it be performed in accordance with the latest revision of reflect the actual conditions.
  • Page 9: Stationary Battery Maintenance Report

    ® A Division of Exide Technologies A Division of Exide Technologies A Division of Exide Technologies WHEN ADVICE IS DESIRED PLEASE FORWARD A DUPLICATE OF THIS REPORT TO YOUR GNB REPRESENTATIVE GB-1000F...
  • Page 10 NOTES...
  • Page 12 North America and Europe and a truly global reach (operations in more than 80 countries) in sales and GNB Industrial Power takes pride in its commitment to a service, GNB Industrial Power is best positioned to satisfy better environment.