Download Print this page

GiBiDi PASS 3 Instructions For Installation Manual page 20

Electronic control unit
Hide thumbs Also See for PASS 3:

Advertisement

UK
ELECTRICAL CONNECTIONS
1-2
220-230V, 50-60 Hz power supply
3-4
12V battery connection; connect the positive (+) to terminal
3, the negative (-) to terminal 4.
5-6
Common wires for buttons, photocell contacts, warning light
and flashing light.
7-6
N.O. contact of closing button
8-6
N.O. contact of start button (opening; see paragraph on
program m ing)
9-6
N.O. contact of pedestrian gate button
10-6
N.C. contact of external photocell
11-6
N.C. contact of opening safety device (frame)
12-6
N.C. contact of internal photocell
13-6
N.C. contact of stop or emergency button
14-15
Antenna coaxial cable connection
16-17
12V DC motor
18-19
12V DC output for auxiliary power supply: photocells, radio
receiver in container, etc. Connect the positive (+) to terminal
18 and the negative
(-) to terminal 19.
20-18
12V DC flashing light
21-18
12V DC warning light
22
AUTOTEST output for safety devices set up for this function.
PROTECTION DEVICES
F1 – F3A
15A protection fuse for 220-230V inputs
F2 – F6, 3A
3A protection fuse for low voltage (12V)
S1 - Radio receiver card (see instructions at end of booklet) or RF
module (see paragraph on programming).
S2 – Mini-photocell control card with autotest.
S3 – Limit switch card inserted underneath the electronic equipment.
MIN. ÷M AX.
FUNCTION
. 1
0 ÷ 1
. 2
0 ÷ 1
. 3
0 ÷ 6
. 4
0 ÷ 6
20
OPENING LIMIT SWITCH (Card S3)
0 = Absent
1 = Present
CLOSING LIMIT SWITCH (Card S3)
0 = Absent
1 = Present
INTERNAL PHOTOCELL (12-6)
0 = Absent / not connected
1 = If intercepted during the closing phase, it stops and immediately inverts the gate motion;
not active in the opening phase.
2 = If intercepted during the closing phase, it stops the gate motion; when the photocell is
freed, the gate restarts opening; the photocell is not active in the opening phase.
3 = If intercepted during the closing or opening phase, it stops the gate motion; when the
photocell is freed, the gate restarts opening.
4 = If intercepted during the closing phase, it stops the gate motion; when it is freed, the
gate restarts closing. The photocell is not active in the opening phase.
5 = If intercepted during the closing phase, it stops and immediately inverts the gate motion.
If intercepted during the opening phase, as soon as it is freed, it stops the opening
m otion and starts closing.
6 = If intercepted during the closing phase, it stops the gate motion; when the photocell is
freed it immediately restarts closing. If intercepted during the opening phase, as soon as
it is freed, it stops the opening motion and starts closing.
EXTERNAL PHOTOCELL (10-6)
0 = Absent / not connected
1 = If intercepted during the closing phase, it stops and immediately inverts the gate motion;
not active in the opening phase.
2 = If intercepted during the closing phase, it stops the gate motion; when the photocell is
freed, the gate restarts opening; the photocell is not active in the opening phase.
3 = If intercepted during the closing or opening phase, it stops the gate motion; when the
photocell is freed, the gate restarts opening.
4 = If intercepted during the closing phase, it stops the gate motion; when it is freed, the
gate restarts closing. The photocell is not active in the opening phase.
5 = If intercepted during the closing phase, it stops and immediately inverts the gate motion.
If intercepted during the opening phase, as soon as it is freed, it stops the opening
m otion and starts closing.
L1 – Power LED
PROGRAM M ING
To set the correct operating values of the equipment, the display D1
and D2 and the keys P1 and P2 are used.
D1 – Displays tens. The dot signals that the num ber indicated by
the display refers to the function to be programmed.
D2 – Displays the unit. The dot signals that the value which is being
increased has exceeded 100.
P1 – Increase key. Holding the key pressed down for 7 seconds, the
display will show zero.
P2 – Program storage key.
Programming procedure
The equipment is already provided with a standard program (default)
as shown in the table.
To access the programming menu press the key P2, the display will
show (.1), i.e. the first programmable function.
If wishing to program the function (.1), again press the P2 key to
enter the subm enu; the display will show the existing program of
the function (.1). If wishing to modify it, press the button P1. After
selecting a suitable program from the submenu, confirm by pressing
the button P2. The program is now stored and the display will show
(.2), i.e. the next programmable function.
To program (.2) carry out the previous operations. If wishing to go
to another program , press the increase button P1 and the display
will scroll forward (.3 - .4 -.5 etc.).
After having pr ogr am m ed all the desir ed functions, exit fr om
programming with the increase key P1 until the display turns off.
In case of error, the program can always be cancelled and the standard
(default) stored by entering the program m ing m enu, selecting the
number 9.9 and confirming with the P2 key.
If a manual manoeuvre of the gate is carried out, ensure that
when the automatic device is reset, it runs the whole opening
phase during the first manoeuvre.
DESCRIPTION
DEFAULT
0
0
0
0

Advertisement

loading